PP R.O.W.
EXIST. LIGHT POLE
LP
EXISTING CENTER LINE ROAD
E
EXISTING BUILDING
6"
EXIST. GAS MAIN
W
EXIST. WATER MAIN
E
EXIST. ELECTRIC LINE
E
PROPOSED UNDERGROUND ELECTRIC
HORIZONTAL SCALE 20
SF
SILT SOCK
EXISTING USE:
VACANT LAND
PROPOSED USE:
SINGLE FAMILY HOUSE
492.7
X 492.7
1. EACH LIFT TO BE COMPACTED WITH VIBRATORY ROLLER.
40
ASPHALT DRIVEWAY SECTION N.T.S.
PROPOSED SPOT ELEVATION
491.5
EXISTING SPOT ELEVATION SILT FENCE
SF
EXISTING STORM SEWER & MH
G
G G
HYD
EXISTING WATER SERVICE & VALVE
VOSBURG
W
ROAD
REQUIRED
PROPOSED
MIN LOT WIDTH
100'
125'
MIN LOT AREA
28,000
24,341 SF *
FRONT SETBACK
50'
41' **
SIDE SETBACK
15'
15
REAR SETBACK
55'
77'
MAX BUILDING HEIGHT
30'
<30'
MAX LOT COVERAGE
20%
18%
W
( REPUTED 49.5' WIDE ) S
S
EXISTING SANITARY SEWER AND MANHOLE
SS
SS
P OH
→
MH
353
SS S
4.
THERE ARE NO WETLANDS ON THE PROPERTY PER WETLAND MAPPING.
5.
THE SUBJECT PROPERTY IS NOT LOCATED WITHIN A FLOODPLAIN PER FEMA MAP 36055C0207H DATED 7/31/2024.
G
7.
ELECTRIC & GAS WILL BE SUPPLIED BY BY RG&E.
8.
SANITARY SEWER SERVICE WILL BE PROVIDED BY THE TOWN OF WEBSTER.
9.
STORM SEWER AND DRAINAGE FACILITIES WILL OWNED AND MAINTAINED BY THE OWNER.
W 132 .16'
OH P →
24,341.1 Sq.Ft. 0.559 Acres to R.O.W.
W SS
A B
6.
SBL #63.07-02-035 N/F CHARLES KORYTKO 541 VOSBURG ROAD L. 10300 D., P. 316
77.4'
G
GARAGE PAD ELEV= 357.0
Lateral connection must be cored. Pneumatic devices or hammering knock-out methods are not acceptable for creating opening for new lateral pipe.
Inserta Tee by Inserta Fittings Co., or approved equal.
Lateral connections must be witnessed by a representative of the District. 7. Notify Pure Waters a minimum of 48 hours in advance of construction for inspection of the lateral connection. Telephone (585) 760-7600, Option 5.
4
MONROE COUNTY PURE WATERS
90
CORED TEE CONNECTION TO EXISTING SEWER N.T.S.
°0
0'
00
"
218.70'
6 35
ROCK
LOCATION SKETCH STAMP:
O.D.
O.D.
A
A 12" 12"MIN.
COMPACTED SELECT FILL
COMPACTED SELECT FILL STONE BEDDING
STONE BEDDING
1/2O.D. B
B
STONE BEDDING OR COARSE AGGREGATE AS DETERMINED BY DEVELOPER'S ENGINEER
UNDISTURBED EARTH
ROCK FIRST CLASS CLASS "B"
PIPE DIA. DIM. A DIM. B UP TO 18"
1.0'
6"
21" TO 36"
1.5'
9"
OVER 36"
1.5'
12"
SPECIAL BEDDING IN UNSTABLE MATERIAL 1. TRENCH BACKFILL SHALL BE AS REQUIRED BY THE HIGHWAY OWNER. 2. SELECT FILL SHALL BE SAND, GRAVEL, AND SIMILAR MATERIAL WHICH SHALL BE FREE FROM CLAY, LOAM, ORGANIC MATERIAL, DEBRIS, FROZEN MATERIAL AND SHALL CONTAIN ONLY SMALL AMOUNTS OF STONE, PEBBLES OR LUMPS OVER ONE INCH IN GREATEST DIMENSION BUT NONE OVER TWO INCHES IN GREATEST DIMENSION. 3. STONE BEDDING SHALL MEAN APPROVED IMPORTED AGGREGATE MEETING THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF TRANSPORTATION, STANDARD SPECIFICATION, JAN 2, 1990 EDITION, AS REVISED, SUBSECTION 703-0201 "CRUSHED STONE". PRIMARY SIZE 1 OR A MIXTURE OF PRIMARY SIZES 1 AND 2. 4. COARSE AGGREGATE SHALL MEAN APPROVED IMPORTED AGGREGATE MEETING THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF TRANSPORTATION, STANDARD SPECIFICATION, JAN 2, 1990 EDITION, AS REVISED, SUBSECTION 703-0201 "CRUSHED STONE". PRIMARY SIZE 3 AND/OR 4 5. THIS FIGURE APPLIES TO SANITARY MAINLINE AND LATERAL PIPE INSTALLATION AS WELL AS FORCEMAINS.
STORM SEWER/SANITARY SEWER BEDDING 354
N.T.S.
SS
355
356
OH P
SBL #63.07-02-033 N/F DALE RENFER 498 ADAMS ROAD L. 8745 D., P. 390
1.5" x 1.5" WOODEN STAKES PLACED 10' O.C.
WORK AREA 12" MIN
CLIENT:
537 VOSBURG RD WEBSTER, NY 14580
DAVID COX PE
PROJECT ENGINEER
NO. DATE BY . . 1 2 3 4 5 6 7 8 9 10 11 12 13
DESCRIPTION .
UNAUTHORIZED ALTERATIONS OR ADDITIONS TO THIS DRAWING IS IN VIOLATION OF STATE EDUCATION LAW ARTICLE 145 SECTION 7209 AND ARTICLE 147 SECTION 7307, THESE PLANS ARE COPYRIGHT PROTECTED. ©
1.5" x 1.5" WOODEN STAKES PLACED 10' O.C. COMPOST SOCK (8" OR 12" TYPICAL) AT END OF SWALES WITH CONCENTRATED AREA TO BE FLOW. PROVIDE PROTECTED TRIPLE STACK CONSIGURATION AS SHOWN
SITE PLAN DS
1"
AREA TO BE PROTECTED
SS
N.T.S.
UNDISTURBED EARTH
CONCRETE ENCASEMENT
A A
Expose face of pipe from crown to invert for 12" along the length of the main. Core hole a minimum of 6" away from existing pipe hubs.
Take necessary precautions to prevent damage to the existing sewer, and to prevent debris from entering the sewer.
B
LIMIT OF TRENCH EXCAVATION
Size of cored opening shall be limited to one-half the nominal diameter of the mainline sewer.
35
15' SIDE SETBACK
"
VOSBURG RD
CONCRETE 3000 PSI
B ROCK CONCRETE (3000 PSI MIN.) UNDISTURBED EARTH CONCRETE CRADLE CLASS "A"
Thoroughly clean surface of existing 5. pipe of foreign matter and loose particles prior to placement of Tee connection.
SF
G
4.
COVERED PORCH
PROPOSED 24' WIDE DRIVEWAY
O.D.
3" MIN. OR 1/4 O.D.
353
AREA:
15.4'
69
'00
A
ST ANNS CT
SITE
"
353 50' F SETB RONT AC K
STORY HOUSE FF=358.3 CANT PARCEL VA
CONTRACTOR SHALL COORDINATE GAS AND ELECTRIC WITH UTILITY COMPANY
8 °1
A
1/2 O.D.
G SS
SBL #63.07-02-034 WEDGE HOLDINGS LLC TH N/F SOU BURG ROAD 537 VOS 1 PROPOSED L. 12803 D., P. 225
55' REAR SETBACK
OH P
SS
D ROA
) IDE
INV=353.0
125.85'
.5' W
3.
SF
( 49
2.
50' FRONT SETBACK
6.0'
ADA MS
PROPOSED SILT SOCK
SF
David Cox
47.5'
7/17/2026 4:45 PM
4
46.7' COVERED ENTRY
6 35 E
G
1.
355
C:\USERS\DCOX.BTMJQN3\ONEDRIVE\DESKTOP\FILES\DEVELOPMENT\PROJECTS\WEBSTER\537 VOSBURG\01_CAD-BIM-MODELS\537 VOSBURG SITE PLAN.DWG
35
41.0'
" SF
W
E
E
O.D.
89
'22 26 1° 11 50.0 SF '
CO PROPOSED WATER SERVICE (1" COPPER FROM PUBLIC MAIN TO CURB STOP & 1" PE FROM CURB STOP TO HOUSE) WITH CURB STOP ON ROW (TYP)
G
G
D
COMPACTED SELECT FILL
SF
SF
W
O O
12"MIN.
172.00'
PROPOSED 4" PVC 355 SDR-21 SANITARY SEWER PIPE AT 2.00% MIN
PROPOSED CURB STOP. SEE DETAIL 1" TAP AND COPPER WATER SERVICE TO THE ROW BY MCWA FOR A SET FEE TO THE OWNER.
A
°1 5
W
OHP
CO
EW
WATER WILL BE PROVIDED BY MCWA
'3 8
354
INV @ TOP OF RISER = 349.0
TA N T GL
LIMIT OF TRENCH EXCAVATION
OHP
SF
STO CR NEY EEK RU N
C
6.
OHP
RISER
EST FOR N DR LAW
10. ALL IMPROVEMENTS SHALL BE MADE IN ACCORDANCE WITH THE CURRENT DEVELOPMENT STANDARDS AND SPECIFICATIONS OF TOWN OF WEBSTER AND MONROE COUNTY.
353
OHP
LAKE ONTARIO
* PRE-EXISTING NON CONFORMING ** AREA VARIANCE REQUIRED.
W
PROPOSED SANITARY SEWER AND MANHOLE
CONNECT TO EX SANITARY SEWER WITH INSERTA-TEE AND RISER. TOP OF EX 24" SAN = 337.10
ENGINEERING
ZONING ANALYSIS
UNDISTURBED SUBSOIL
20
1"=20'
PROPOSED WATER SERVICE W/ HYDRANT & VALVE
WV
R-2
EXISTING TREE/BRUSH LINE
PROPOSED STORM SEWER, INLET MH, CB & END SECTION
W
PROPOSED ZONING:
D
PROPOSED MINOR CONTOUR
R-2
ER R
521
0.32 ACRES
EXISTING ZONING:
BAK
PROPOSED MAJOR CONTOUR
10
0
PROPOSED TREE/BRUSH LINE
520
CB
G
8" CRUSHED STONE (2 LIFTS) (NYSDOT ITEM 304.12)
DISTURBANCE AREA:
T DR
EXISTING MINOR CONTOUR
0.559 ACRES (24,341 SF)
FORES
521
TOTAL PARCEL AREA:
RD
EXISTING MAJOR CONTOUR
3.
MS
520
D
EXIST. GAS VALVE
GV
PROPOSED CONCRETE
537 VOSBURG RD
1.5" 9.5 MIX ASPHALT (NYSDOT ITEM NO 608.020102)
MIRAFI 500X GEOTEXTILE FABRIC OR APPROVED EQUAL
EXISTING FENCE
PROPOSED BUILDING
63.07-02-034
PARCEL ADDRESS:
1.5" 19.0 MIX ASPHALT (NYSDOT ITEM NO 608.020102) EXIST. ELECTRIC HANDHOLE
PROPOSED EASEMENT LINE
6"
TAX ACCOUNT NUMBER:
2.
EXIST. ELECTRIC MANHOLE
MH
HH
EXISTING EASEMENT LINE
LIMITS OF DRIVEWAY EXCAVATION VARIES
1.
ADA
R.O.W.
EXISTING ELECTRIC LINE & POLE
OHW
PROPERTY BOUNDARY
S
COX
SITE DATA
LEGEND:
SECTION
1"
COMPOST SOCK (8" OR 12" TYPICAL)
PE 4710
DS
537 VOSBURG
WATER FLOW
WEBSTER WORK AREA
MONROE NOTES: 1. ALL MATERIAL TO MEET SPECIFICATIONS. 2. COMPOST SOCKS FILL TO MEET APPLICATION REQUIREMENTS. 3. FILTER MEDIA TO BE DISPERSED ON SITE, AS DETERMINED BY ENGINEER.
PLAN
S
COMPOST SOCKS FOR SEDIMENT CONTROL
APPROVED BY APPROVED BY APPROVED BY
N.T.S.
TOWN ENGINEER
TOWN SEWER DEPT
TOWN HIGHWAY SUPERINTENDENT
DATE
PROJECT NO.:
2026217
DATE DRAWING NO.:
C-101
DATE DATE:
APPROVED BY
MCWA
DATE
JULY 2026