FINALfor SITE PLANS
COBBLESTONE PLACE PHAS 1025 RAVENSIDE LANE SITUATE IN:
TOWN OF WEBSTER- MONROE COUNTY - STATE OF NEW YORK TARGET
4
ROAD RIDGE
NY 40
SIDE
COBBLESTONE PLACE AT WEBSTER
LOCATION MAP NOT TO SCALE
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
840 HANSHAW RD, STE 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
COPYRIGHT ã 2026 MARATHON ENGINEERING
www.marathoneng.com
LA N
TALLGRASS LANE
SHOECRAFT
ROAD
RAVEN
E
NORTH
MMONS WEBSTER CO BOULEVARD
WEBSTER PLAZA
HARMONY STATION
HARD ROAD
TJ MAX
COBBLESTONE PLACE PHASE 2
SURVEY NOTES
3.
BOUNDARY - BOUNDARY CONSTRUCTED FROM THE MAPS AND DOCUMENTS REFERENCED ON THIS SHEET.
4.
DATUM - THE VERTICAL DATUM IS NAVD88. THE HORIZONTAL DATUM IS NAD83 CENTRAL ZONE.
5.
THE PROPERTY IS LOCATED IN ZONE 'X' AND IS LOCATED GRAPHICALLY IN THE FLOODPLAIN AS SHOWN ON COMMUNITY PANEL No 36055C0229G, DATED 08/28/2008
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
www.marathoneng.com
1. 2. 3.
SUBDIVISION PLAN OF R.T. GOLD, INC FILED NOVEMBER 16, 1998 AS LIBER 298, PAGE 39 SUBDIVISION PLAT - WEBSTER GOLF TEE MIXED USE SITE PHASE 1 FILED FEBRUARY 1, 2011 AS LIBER 340, PAGE 70 RESUBDIVISION OF LOT AR-1C OF THE WEBSTER GOLF TEE SUBDIVISION, LIBER 352 OF MAPS PAGE 19 FILED SEPTEMBER 23, 2020 AS LIBER 361, PAGE 45
ADJACENT PROPERTY LINE PROJECT PROPERTY LINE EASEMENT LINE EXISTING GAS MAIN & VALVE EXISTING ELECTRIC CONDUIT & STRUCTURE EXISTING STORM MAIN, MANHOLE, AND INLET EXISTING SANITARY MAIN & MANHOLE EXISTING WATER MAIN, VALVE, & HYDRANT EXISTING CONTOUR DEMOLISH UTILITY
X
TREE REMOVAL
REMOVE/MILL ASPHALT PARKING COUNT
FINALfor SITE PLANS
REFERENCES
STATE OFNEW YORK
THE CONTRACTOR SHALL NOTIFY DIG SAFELY NEW YORK (1-800-962-7962) FOR A UTILITY STAKEOUT 48 HOURS IN ADVANCE OF COMMENCING WORK. STAKEOUT OF PRIVATE UTILITIES SHALL BE COORDINATED WITH THE OWNER.
NORTH
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
BY
TOWN OF WEBSTER
2.
THE EXISTING UNDERGROUND UTILITIES WERE PLOTTED BASED ON RECORD MAPPING SUPPLIED BY OTHERS. THE ENGINEER MAKES NO WARRANTY AS TO THE LOCATION, SIZE, TYPE, ELEVATION, AND/OR NUMBER OF EXISTING UTILITIES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE HORIZONTAL AND VERTICAL LOCATION OF UTILITIES IN THE VICINITY OF THE NEW INFRASTRUCTURE. · SANITARY SEWERS WERE PLOTTED FROM RECORD MAPS RECEIVED FROM THE TOWN OF WEBSTER ON 09/25/2024 ·· SANITARY SEWER DATA WAS RECORDED IN THE FIELD BY MARATHON ENGINEERING ON 10/09/2024 · WATER SERVICES AND MAINS WERE PLOTTED FROM RECORD MAPS RECEIVED FROM MCWA ON 09/11/2024 · STORM SEWERS RECORD MAPS WERE NOT RECEIVED ·· STORM SEWER DATA WAS RECORDED IN THE FIELD BY MARATHON ENGINEERING ON 10/09/2024 · UNDERGROUND GAS SERVICES AND MAINS WERE PLOTTED FROM RECORD MAPS RECEIVED FROM RG&E ON 09/13/2024 · UNDERGROUND ELECTRIC LINES WERE PLOTTED FROM RECORD MAPS RECEIVED FROM RG&E ON 09/13/204 · CAD UTILITY AS-BUILT FILE SUPPLIED BY PASSERO ASSOCIATES.
1025 RAVENSIDE LANE MONROECOUNTY
1.
1764-25 1"=30' RLB RPB 05/13/2025 REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
ROBERT P. BRINGLEY
DRAWING TITLE:
EXISTING CONDITIONS AND DEMOLITION PLAN 1 of 9 SHEET No:
V1.0
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
NORTH
ADJACENT PROPERTY LINE PROJECT PROPERTY LINE
ROCHESTER LOCATION
EASEMENT LINE
STANDARD ABBREVIATIONS
SIGN
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0
EXISTING POWER POLE
ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
LIGHT POLE EXISTING FENCE (DESCRIPTION)
CURB PROPOSED SIDEWALK
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
CONSTRUCTION NOTES
PROJECT STATISTICS FOR LOT 1025
1.
1. GENERAL: 1.1 DEVELOPER -
BRICKWOOD MANAGEMENT 25 SILVERLIGHT WAY ROCHESTER, NY 14624
1.2 PROPERTY ADDRESS -
1025 RAVENSIDE LANE WEBSTER, NY 14580
1.3 TAX ACCOUNT -
079.15-1-8.003/SEN2
1.4 PARCEL AREA -
5.0 ACRES
2.
DIMENSIONS SHOWN, WHERE APPLICABLE, SHALL BE FROM THE FACE OF CURB UNLESS SPECIFICALLY CALLED OUT OTHERWISE.
4.
CLEARING AND GRUBBING SHALL BE LIMITED TO THE SITE BOUNDARIES OR WITHIN THE "WORK LIMIT LINE" AS DEFINED ON THE PLAN. TREES AND OBJECTS DESIGNATED FOR REMOVAL SHALL BE COORDINATED AND FIELD VERIFIED WITH PROJECT ON-SITE REPRESENTATIVE. ALL MATERIALS SHALL BE LEGALLY DISPOSED OF OFF-SITE OR RETURNED TO OWNER AS DIRECTED BY CONTRACT DOCUMENTS. ALL ITEMS NOT SPECIFICALLY CALLED OUT TO BE REMOVED SHALL REMAIN.
MHR - MEDIUM HIGH RESIDENTIAL
2.2 CODE REQUIREMENTS BULK REQUIREMENTS FRONT SETBACK MIN. BUFFER AREA MIN. PARKING SETBACK MAXIMUM BUILDING HEIGHT MAXIMUM BUILDING LENGTH MIN. DISTANCE BETWEEN BUILDINGS MAXIMUM DENSITY (8 UNITS/ ACRE) MINIMUM PARKING SPACES
5. REQUIRED 75' 50' 50' 3 STORIES 165'* 40' 40 94 (2 UNITS/ ACRE)
BOUNDARY INFORMATION WAS TAKEN FROM SHEET V1.0 PREPARED BY MARATHON ENGINEERING DATED 09/13/2023 AND IS SHOWN FOR GRAPHICAL REPRESENTATION ONLY.
3.
2. ZONING REGULATIONS: 2.1 ZONING DISTRICT -
THE CONSTRUCTION STAKEOUT SHALL BE PERFORMED BY A LICENSED LAND SURVEYOR USING CONTROL PROVIDED ON THE "LAYOUT PLAN". THE BUILDING FOOTPRINT(S), DATED JULY 20, 2023 WERE PROVIDED BY ALVIN HAZLEWOOD ARCHITECT. DISCREPANCIES WITH BUILDING(S), CONTROL POINTS, AND/ OR TIE DIMENSIONS SHALL BE REPORTED TO THE DESIGN ENGINEER (PRIOR TO THE INSTALLATION OF IMPROVEMENTS) FOR COORDINATION AND CLARIFICATION.
PROVIDED 16' ** 16'** 0'** 3 STORIES 242'* 36'** 48*** (9.6 UNITS/ ACRES) 89(11 GARAGE)** (1.85 SPACES/ UNIT)
2.3 VARIANCES *EXCEPT WHERE PAVED ACCESSIBILITY TO ALL SIDES OF THE BUILDING THEN MAX LENGTH MAY BE INCREASED TO 250'. **VARIANCES GRANTED 3/13/25 ***VARIANCES GRANTED 3/10/15 FOR 12 UNITS/ ACRE DENSITY,
GENERAL NOTES 1.
2.
3.
THE CONTRACTOR SHALL COORDINATE INSTALLATION OF UTILITY WORK WITH OTHER SITE UTILITIES (I.E. GAS, ELECTRIC, LIGHTING, COMMUNICATIONS) TO AVOID POTENTIAL INSTALLATION CONFLICTS.
6.
7.
"C" SERIES DRAWINGS. THE "C" SERIES DRAWINGS COVER SITE RELATED IMPROVEMENTS OUTSIDE THE BUILDING ENVELOPE. THE BUILDING ENVELOPE INCLUDES ALL AREA WITHIN 5' OUTSIDE OF THE BUILDING'S EXTERIOR WALL.
9.
THE EXISTING UNDERGROUND UTILITIES WERE PLOTTED BASED ON RECORD MAPPING SUPPLIED BY OTHERS. THE ENGINEER MAKES NO WARRANTY AS TO THE LOCATION, SIZE, TYPE, ELEVATION, AND/OR NUMBER OF EXISTING UTILITIES. THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE HORIZONTAL AND VERTICAL LOCATION OF UTILITIES IN THE VICINITY OF THE NEW INFRASTRUCTURE.
10. PERMIT(S) - PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL OBTAIN THE NECESSARY PERMITS
UTILITY STAKEOUT - THE CONTRACTOR SHALL NOTIFY UDIG NY (1-800-962-7962) FOR A UTILITY
THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE TO EXISTING PAVEMENT, CURBS, WALKS, LAWNS, TREES, ETC. CAUSED BY THEIR CONSTRUCTION OPERATIONS. ALL DAMAGE SHALL BE REPAIRED OR REPLACED BY THE CONTRACTOR TO THE OWNER'S SATISFACTION AT NO ADDITIONAL EXPENSE.
STAGING - AS DEFINED BY THE CONTRACT DOCUMENTS THE CONTRACTOR SHALL CONSTRUCT A SECURE
5.
STAGING AREA FOR STORAGE OF EQUIPMENT, MATERIALS, EMPLOYEE PARKING AND OFFICE SPACE. IF THE AREA/METHOD IS NOT SPECIFICALLY DEFINED ON THE DOCUMENTS THEN IT SHALL BE COORDINATED WITH THE OWNER'S ON-SITE REPRESENTATIVE.
THE CONTRACTOR SHALL PROVIDE SATISFACTORY VEHICULAR ACCESS TO ALL ADJOINING PROPERTIES, PRIVATE ROADWAYS, PARKING FACILITIES, AND PUBLIC STREETS DURING CONSTRUCTION.
6.
PRIOR TO AND THROUGHOUT CONSTRUCTION, THE CONTRACTOR SHALL POST SIGNAGE IN CONFORMANCE WITH THE REQUIREMENTS OF THE LOCAL MUNICIPALITY AND OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA). JOB SAFETY AND MAINTENANCE AND PROTECTION OF TRAFFIC IS THE RESPONSIBILITY OF THE CONTRACTOR.
THE CONTRACTOR'S WORK SCOPE INCLUDES BUT IS NOT LIMITED TO THE FOLLOWING AT PROJECT CLOSE-OUT TO THE SATISFACTION OF OWNER'S ON-SITE REPRESENTATIVE: l REMOVAL OF ANY CONSTRUCTION DEBRIS. l CLEANING PAVEMENT AND WALKWAY SURFACES. l RESTORATION OF ALL DISTURBED GRASS AND LANDSCAPED AREAS. l PROVIDING BONDS, GUARANTEES, CERTIFICATIONS, ETC. AS REQUIRED BY CONTRACT DOCUMENTS. l PROVIDING REDLINES FOR RECORD DRAWING. l COMPLETION OF FINAL PUNCH LIST ITEMS.
7.
PUBLIC STREETS, PRIVATE DRIVES AND PARKING FACILITIES SHALL BE KEPT FREE OF FOREIGN MATERIALS. ALL AREAS SHALL BE SWEPT CLEAN AT THE END OF EACH WORKING DAY AND/OR AS DIRECTED BY THE OWNER'S ON-SITE REPRESENTATIVE.
TOWN OF WEBSTER 1764-25 1"=30' RLB RPB 05/13/2025
REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
APPLICABILITY - THE NOTES AND INFORMATION PROVIDED ON THIS SHEET ARE APPLICABLE TO ALL
STAKEOUT 48 HOURS IN ADVANCE OF COMMENCING WORK. STAKEOUT OF PRIVATE UTILITIES SHALL BE COORDINATED WITH THE OWNER.
4.
8.
BY
1025 RAVENSIDE LANE MONROECOUNTY
FINALfor SITE PLANS
NEW PAVEMENT
STATE OFNEW YORK
www.marathoneng.com
PROPOSED PARKING SPACE COUNT
ALL EXCAVATIONS SHALL BE BACKFILLED/BARRICADED TO THE SATISFACTION OF THE
STORAGE OF EQUIPMENT AND MATERIALS SHALL BE WITHIN A SPECIFIED AND SECURED AREA AS DETERMINED IN CONTRACT DOCUMENTS OR AS SPECIFIED BY THE OWNER'S ON-SITE REPRESENTATIVE.
FROM THE APPLICABLE MUNICIPALITY OR AGENCY. THE CONTRACTOR IS RESPONSIBLE FOR ALL BONDS AND INSURANCES AND THE OWNER IS RESPONSIBLE FOR PERMIT FEES UNLESS OTHERWISE STATED IN THE OWNER/ CONTRACTOR AGREEMENT
11. INTERIM CONDITIONS - THE CONTRACTOR IS RESPONSIBLE TO MAINTAIN POSITIVE DRAINAGE AWAY FROM BUILDINGS AND WITHIN PROJECT AREA TO A STABILIZED OUTLET THROUGHOUT THE CONSTRUCTION PERIOD. THIS MAY REQUIRE INTERIM GRADING, SHIMMING OF PAVEMENT ETC. THAT IS NOT SPECIFICALLY SHOWN ON THE PLANS AND SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR.
ROBERT P. BRINGLEY
12. ARCHITECTURAL LAYOUT LAYOUT OF FOOTPRINT OF BUILDING DATED 1/23/25
DRAWING TITLE:
LAYOUT PLAN
2 of 9 SHEET No:
OWNER'S REPRESENTATIVE AT THE CONCLUSION OF EACH WORKING DAY.
C1.0
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
NORTH
EASEMENT LINE ADJACENT PROPERTY LINE PROJECT PROPERTY LINE
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0
STORM SEWER, MANHOLE & FIELD/DROP INLET SANITARY SEWER WITH MANHOLE
ITHACA LOCATION
EXISTING GAS MAIN & VALVE
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
EXISTING ELECTRIC CONDUIT & STRUCTURE EXISTING TELEPHONE CONDUIT & STRUCTURE
CENTERLINE OF SWALE
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE
UTILITY NOTES 1.
INCHES MEASURED FROM THE OUTSIDE OF THE PIPES AT THE POINT OF CROSSING. ONE FULL STANDARD LAYING LENGTH OF WATER MAIN PIPE SHALL BE CENTERED UNDER OR OVER THE SEWER SO THAT BOTH JOINTS WILL BE AS FAR FROM THE SEWER AS POSSIBLE. IN ADDITION. WHEN THE WATER MAIN PASSES UNDER A SEWER, ADEQUATE STRUCTURAL SUPPORT (COMPACTED SELECTED FILL) SHALL BE PROVIDED FOR THE SEWER TO PREVENT EXCESSIVE DEFLECTION OF JOINTS AND SETTLING OF THE SEWER ON THE WATER MAIN. MINIMUM HORIZONTAL SEPARATION BETWEEN PARALLEL WATER MAINS AND SEWER PIPES (INCLUDING MANHOLES AND VAULTS) SHALL BE 10 FEET MEASURED FROM THE OUTSIDE OF THE PIPES. MANHOLES OR VAULTS.
1.1 MATERIALS · MAINS - PIPING SHALL BE POLYVINYL CHLORIDE (PVC) WITH ENDS SUITABLE FOR ELASTOMERIC GASKET JOINTS, AND A MINIMUM WALL THICKNESS OF SDR-35. PIPING AND FITTINGS SHALL MEET: · ASTM D-3034 (4" THRU 15") · ASTM F-679 (18" THRU 48") · LATERALS - PIPING SHALL BE POLYVINYL CHLORIDE (PVC) WITH ENDS SUITABLE FOR ELASTOMERIC GASKET JOINTS, AND A MINIMUM WALL THICKNESS OF SDR-21. PIPING AND FITTINGS SHALL MEET ASTM D-2241. · JOINTING MATERIALS - SHALL BE BELL-AND-SPIGOT WITH INTEGRAL PUSH ON TYPE ELASTOMERIC GASKET JOINTS, GASKET MATERIAL TO BE NEOPRENE MEETING ASTM D-3212. · MANHOLES - SHALL BE PRECAST CONCRETE WITH NEOPRENE GASKETS MEETING ASTM C-478 & ASTM C-443.
TOWN OF WEBSTER
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCWA COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS
05/26/26 07/06/26
JPC MCWA COMMENTS JPC ISSUED MYLAR
COPYRIGHT ã 2026 MARATHON ENG.
WITH THE LATEST REGULATIONS OF THE MUNICIPALITY AND ALL THERMOPLASTIC PIPE SHALL BE INSTALLED IN ACCORDANCE WITH ASTM D-2321.
2.2 MATERIALS - THE CONTRACTOR MAY USE THE FOLLOWING PIPE MATERIAL FOR THE MAIN SEWER AS ALLOWED BY THE MUNICIPALITY, PROVIDING THAT THE ROUGHNESS COEFFICIENT ("N" FACTOR) IS 0.013 OR BETTER: · REINFORCED CONCRETE PIPE (RCP), CLASS III · HIGH DENSITY CORRUGATED POLYETHYLENE PIPE (PE), AASHTO M-294, TYPE S, ASTM D-3350.
ROBERT P. BRINGLEY
DRAWING TITLE:
2.3 ROOF DRAINAGE - ALL ROOF DRAINAGE SHALL BE COLLECTED AND PIPED TO THE STORM SEWER SYSTEM UNLESS SPECIFIED OTHERWISE.
1.3 FLOOR DRAINS - FLOOR DRAINS, IF CONSTRUCTED IN THE PROJECT. MUST BE CONNECTED TO THE
CONDUCTED AFTER THE FINAL BACKFILL HAS BEEN IN PLACE AT LEAST 30 DAYS. NO PIPE SHALL EXCEED A DEFLECTION OF 5%. IF THE DEFLECTION TEST IS TO BE RUN USING A RIGID BALL OR MANDREL. IT SHALL HAVE A DIAMETER EQUAL TO 95% OF THE INSIDE DIAMETER OF THE PIPE. THE TEST SHALL BE PERFORMED WITHOUT MECHANICAL PULLING DEVICES.
6/17/25 7/15/25 9/26/25 12/23/25 02/17/26
2.1 REGULATIONS - STORM SEWERS AND APPURTENANCES SHALL BE CONSTRUCTED IN CONFORMANCE
EXCEED 100 GALLONS PER INCH DIAMETER PER MILE OF PIPE PER DAY FOR THE SANITARY SEWER. IF AN AIR TEST IS USED, THE TEST AS A MINIMUM SHALL CONFORM TO THE PROCEDURE DESCRIBED IN ASTM F1417 ENTITLED STANDARD PRACTICE FOR INSTALLATION ACCEPTANCE OF PLASTIC NON-PRESSURE SEWER LINES USING LOW-PRESSURE AIR. SANITARY MANHOLES SHALL BE VISUALLY INSPECTED AND TESTED FOR LEAKAGE BY EX FILTRATION OR VACUUM. AIR VACUUM TESTING OF MANHOLES SHALL BE PERFORMED IN ACCORDANCE WITH ASTM C-1244.
1.4 TESTING - DEFLECTION TESTS SHALL BE PERFORMED ON ALL FLEXIBLE PIPE. THE TEST SHALL BE
REVISION
2. STORM
1.2 INFILTRATION/ EXFILTRATION - MAXIMUM ALLOWABLE INFILTRATION OR EXFILTRATION SHALL NOT
FLOOR DRAINS DO NOT INCLUDE FOUNDATION OR FOOTER DRAINS INSTALLED TO INTERCEPT UNCONTAMINATED GROUND WATER. ALL DISCHARGES FROM THE FLOOR DRAINS TO THE SANITARY SEWER MUST COMPLY WITH THE EFFLUENT LIMITS OF THE LOCAL AND/OR THE MONROE COUNTY SEWER USE LAW.
1764-25 1"=30' RLB RPB 05/13/2025
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
1.5 SEPARATION - MINIMUM VERTICAL SEPARATION BETWEEN WATER MAINS AND SEWER LINES SHALL BE 18
SANITARY
BY
1025 RAVENSIDE LANE MONROECOUNTY
FINALfor SITE PLANS
OVERHEAD WIRE AND UTILITY POLE
STATE OFNEW YORK
www.marathoneng.com
WATER MAIN WITH HYDRANT & GATE VALVE
2.4 TESTING - UPON COMPLETION OF SYSTEM INSTALLATION, THE MAIN SEWER SYSTEM AND LEADS TO STRUCTURES SHALL BE FLUSHED AND LAMPED TO THE SATISFACTION OF THE MUNICIPALITY.
3.
WATER 3.1 SEE SHEET C5.2 FOR MONROE COUNTY WATER AUTHORITY AND MONROE COUNTY DEPARTMENT OF
Monroe County Department of Public Health These plans for Public Water System Extension / Improvement are hereby approved pursuant to 10NYCRR5 of the State Sanitary Code subject to conditions of Approval
3 of 9
Director of Public Health
PUBLIC HEALTH WATER NOTES..
UTILITY PLAN
By
Public Health Engineer
Date
C2.0
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
NORTH
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
EROSION CONTROL NOTES 1.
3.
ALL CONTRACTORS AND SUB-CONTRACTORS SHALL CERTIFY WITHIN THE SWPPP THAT THEY WILL IMPLEMENT AND MAINTAIN STORM WATER MANAGEMENT PRACTICES.
EROSION CONTROL (EC) MEASURES INSTALLED AND MAINTAINED BY THE SITE WORK CONTRACTOR ARE SUBJECT TO THE REVIEW AND APPROVAL OF THE: MUNICIPALITY, DESIGN ENGINEER, NYSDEC, AND OWNER'S REPRESENTATIVE. IMMEDIATE ACTION BY THE CONTRACTOR SHALL BE TAKEN IF ADDITIONAL OR CORRECTIVE MEASURES ARE REQUIRED BY ANY ONE OF THESE CITED REVIEWERS. EROSION CONTROL MEASURES NOT SPECIFICALLY SHOWN ON CONTRACT DRAWINGS (I.E.., STRAW BALES, COLLARS, FABRICS, ETC.) SHALL BE INSTALLED AS WARRANTED BY FIELD CONDITIONS, AND AS DIRECTED BY THE AFOREMENTIONED REVIEWERS.
4.
5.
6.
7.
AS DESIGN ENGINEER, OUR OFFICE HAS NOTIFIED THE OWNER OF THE INSPECTION REQUIREMENTS UNDER GP-0-25-001. DISTURBANCES OF 1.0 ACRE OR GREATER REQUIRE THAT THE OWNER FILE A NOTICE OF INTENT (NOI) AND A SWPPP WITH THE NYSDEC UNDER STATE POLLUTANT DISCHARGE ELIMINATION SYSTEM (SPDES) GENERAL PERMIT #GP-0-25-001. THE REGULATIONS REQUIRE THAT A LICENSED PROFESSIONAL COMPLETE A WEEKLY INSPECTION (THROUGHOUT THE PERIOD OF LAND DISTURBANCE). PRE-CONSTRUCTION - THE APPROPRIATE EROSION CONTROL MEASURES AS DEFINED BY THE CONSTRUCTION DOCUMENTS SHALL BE INSTALLED PRIOR TO THE START OF ANY CONSTRUCTION ACTIVITIES.
UPON COMPLETION OF THE STRIPPING OPERATION, STOCKPILES SHALL BE STABILIZED IN ACCORDANCE TO NYSDEC REGULATIONS. SLOPES - UPON COMPLETION OF GRADING, SLOPES WITH A GRADIENT OF ONE FOOT VERTICAL TO THREE FEET HORIZONTAL (1 ON 3) OR GREATER SHALL BE: TOPSOILED, SEEDED, FERTILIZED AND MULCHED OR TREATED AS SPECIFIED ON CONTRACT DRAWINGS.
THE CONTRACTOR SHALL APPLY WATER AND/OR CALCIUM CHLORIDE, AS CONDITIONS WARRANT, TO CONTROL WIND BORN EROSION. THIS MEASURE APPLIES TO: HAUL ROADS, CUT AND FILL OPERATIONS, SUB-BASE AND ANY OTHER EXPOSED SURFACES.
THE STORM WATER POLLUTION PREVENTION PLAN (SWPPP), WHICH INCLUDES THE "GRADING PLAN", "EROSION CONTROL PLAN", "EROSION CONTROL NOTES", ALONG WITH THE "DRAINAGE REPORT", DEFINES AND MEETS THE REQUIREMENTS OF THE NEW YORK STATE DEPARTMENT OF ENVIRONMENTAL CONSERVATION (NYSDEC) LATEST STORM WATER REGULATIONS.
2.
EARTHWORK NOTES
8.
9.
OPERATION & MAINTENANCE - THROUGHOUT THE PERIOD OF CONSTRUCTION AND PRIOR TO ESTABLISHING FINAL GROUND COVER THE SITE CONTRACTOR IS RESPONSIBLE FOR THE OPERATION AND MAINTENANCE OF THE TEMPORARY EROSION CONTROL MEASURES. FOR EXAMPLE, THE SILTATION FACILITIES SHALL BE RE-EXCAVATED WHEN THE VOLUME (3600 CUBIC FEET/DISTURBED ACRE) IS REDUCED BY ONE-HALF OR MORE OF ITS SPECIFIED CAPACITY AND/OR THE MATERIAL IS WITHIN ONE FOOT OF THE DISCHARGE POINT.
10. WORK STOPPAGE - ALL DISTURBED AREAS NOT TO BE WORKED WITHIN 14 DAYS MUST BE SEEDED WITHIN 7 DAYS FROM THE LAST CONSTRUCTION ACTIVITY IN THAT AREA.
11. TEMPORARY STABILIZATION - TEMPORARY STABILIZATION SHALL REQUIRE 4 TONS OF STRAW/ ACRE OF DISTURBANCE PLACED WITH TACKIFIER OR ROLLED WITH A TRACKED VEHICLE TO ENSURE NOT DISPLACED.
12. WINTER STABILIZATION - ALL WINTER STABILIZATION METHODS IDENTIFIED IN THE NYS 'BLUE BOOK' SHALL BE FOLLOWED FOR ANY DISTURBANCE OR NON-STABILIZED AREAS FROM NOVEMBER 15TH - APRIL 1ST.
13. SUBSOIL RESTORATION - ALL AREAS TO BE RESTORED AS LAWN SHALL BE RESTORED PER CHAPTER 5 (5.1.6) OF THE NEW YORK STATE STORMWATER DESIGN MANUAL AND THE SOIL RESTORATION TABLE (TABLE 5.3 - SOIL RESTORATION REQUIREMENTS) SHOWN ON THE PLANS. THE PROJECT SOILS ARE HYDROLOGIC SOIL GROUP _ AND SHALL BE RESTORED AS SPECIFIED. 14. SEDIMENT BASINS - THE PROPOSED BIORETENTION FACILITIES 1AND 2 WILL BE UTILIZED AS SEDIMENT BASINS DURING CONSTRUCTION. THE CONTRACTOR WILL BE REQUIRED TO REMOVE THE SEDIMENT AND CLEARED TO FINAL GRADE AFTER THE SITE HAS BEEN STABILIZED
ANY NEW CHANNELS AND BANKS OF SEDIMENT BASIN/TRAP. SITE GRADING: l COMPLETE CLEARING AND GRUBBING. 1. l PLACE EROSION CONTROL MEASURES AT TOPSOIL STOCKPILES AND STRIP TOPSOIL. l INSTALL ADDITIONAL EROSION AND SEDIMENT CONTROLS ACCORDING TO PLAN. l STRIP AND STOCKPILE TOPSOIL AND GRADE SITE. l STABILIZE DENUDED AREAS AND STOCKPILES IN AREAS WHERE DISTURBANCE ACTIVITIES HAVE TEMPORARILY OR PERMANENTLY CEASED, STABILIZATION MEASURES SHOULD BE INITIATED BY THE END OF THE NEXT BUSINESS DAY AND COMPLETED WITHIN 14 DAYS (WITHIN 7 DAYS FOR SITES WITH OVER 5 ACRES OF DISTURBANCE OR DISCHARGES TO A 303D WATERBODY, OR WITHIN 3 DAYS DURING WINTER, NOVEMBER 15TH TO APRIL 1ST). INFRASTRUCTURE (UTILITIES, PARKING LOT, ETC.): 2. l CONSTRUCT STAGING AND MATERIALS STORAGE AREA. l INSTALL UTILITIES. BUILDING/ROAD CONSTRUCTION: l APPLY STONE TO ROADS AND PARKING AREAS. l COMPLETE GRADING, REAPPLY TOPSOIL, AND INSTALL PERMANENT SEEDING, FERTILIZER AND MULCH. l COMPLETE FINAL PAVING. FINAL STABILIZATION AND LANDSCAPING: l REMOVE ACCUMULATED SEDIMENT FROM SEDIMENT BASIN/TRAP. l REMOVE ALL SEDIMENT CONTROL PRODUCTS AFTER SOILS ARE STABILIZED. l INSTALL INFILTRATION/BIORETENTION PRACTICE ONCE ALL DISTURBED UPSTREAM SOILS ARE STABILIZED.
FOLLOWING APPLICABLE ITEMS AS DEFINED BY CONTRACT DOCUMENTS: l SITE DEMOLITION - REMOVAL AND DISPOSAL OFF-SITE IN A LEGAL MANNER; STRUCTURES, UTILITIES, PAVEMENTS, ETC. l CLEARING AND GRUBBING - REMOVAL AND DISPOSAL OFF-SITE IN A LEGAL MANNER; TREES, BRUSH, STUMPS, ETC. l TOPSOIL STRIPPING - STRIP AND STOCKPILE TOPSOIL FOR REUSE. EXCESS TOPSOIL MAY BE REMOVED FROM SITE WITH APPROVAL BY OWNER AND MUNICIPALITY.
TOWN OF WEBSTER 1764-25 1"=30' RLB RPB 05/13/2025
REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
THE CONTRACTOR IS RESPONSIBLE FOR: l ESTIMATE - COMPLETION OF A QUANTITY TAKEOFF TO DETERMINE THE VOLUME OF CUT, FILL, AND TOPSOIL.
COMPARE AND COORDINATE WITH INFORMATION PROVIDED BY THE DESIGN ENGINEER. l GRADE TOLERANCES - ESTABLISHING DESIGN SUBGRADE ELEVATIONS TO WITHIN ONE TENTH OF ONE FOOT
(0.10') IN PAVEMENT AREAS (INCLUDING WALKS) AND TO WITHIN THIRTY-THREE HUNDREDTHS OF ONE FOOT (0.33') FOR ALL REMAINING AREAS. l COMPACTION - ACHIEVING THE SPECIFIED MINIMUM COMPACTION VALUES FOR EMBANKMENT/FILL AREAS. THE TERMS "FILL" AND EMBANKMENT" ARE INTERCHANGEABLE. l CUTS - ONCE EXCAVATIONS ARE SHAPED TO THE DESIGN GRADES THE AREAS SHALL BE PROTECTED TO ASSURE THAT THE INTEGRITY OF MATERIAL IS NOT COMPROMISED BY CONSTRUCTION VEHICLES AND/OR IMPROPER DRAINAGE. AREAS DETERMINED BY CONTRACTOR TO BE NOT SUITABLE FOR SUBGRADE PLACEMENT SHALL BE IMMEDIATELY REPORTED WHEN THE SUBGRADE IS ESTABLISHED TO OWNER'S REPRESENTATIVE. STABILIZATION MEASURES FOR CUT AREAS MAY BE CONSIDERED BY OWNER'S REPRESENTATIVE AS A CHANGE TO THE BASE CONTRACT.
3. TESTING - THE FOLLOWING MAXIMUM DRY DENSITIES SHALL BE ACHIEVED AS MEASURED BY THE MODIFIED PROCTOR METHOD ASTM D-1557: l 95% UNDER PAVEMENTS, WALKS, AND IN STRUCTURAL FILL AREAS l 85% IN REMAINING AREAS
ROBERT P. BRINGLEY
DRAWING TITLE:
GRADING AND EROSION CONTROL PLAN
THE AGREEMENT BETWEEN THE OWNER AND CONTRACTOR SHALL DEFINE THE NUMBER OF TESTS AND RESPONSIBILITY. WE RECOMMEND IN EMBANKMENT AREAS ONE PER LIFT AND/OR ONE PER 1,000 CUBIC YARDS.
15. CONSTRUCTION SEQUENCE - . BEFORE ANY SITE GRADING ACTIVITIES BEGIN: l INSTALL STABILIZED CONSTRUCTION ENTRANCE. l PROTECT EXISTING VEGETATION AND ENVIRONMENTAL FEATURES TO REMAIN. l INSTALL PERIMETER SEDIMENT CONTROLS. l CLEAR AND GRUB FOR WATER DIVERSIONS AND SEDIMENT BASIN/TRAP. l CONSTRUCT DIVERSION SWALES AND SEDIMENTATION BASINS/TRAPS. STABILIZE SOILS OF
PREPARATION - PRIOR TO START OF EARTHWORK OPERATIONS THE CONTRACTOR SHALL COMPLETE THE
BY
1025 RAVENSIDE LANE MONROECOUNTY
FINALfor SITE PLANS
STATE OFNEW YORK
www.marathoneng.com
4.
5.
LIFT THICKNESS - THE MAXIMUM LIFT THICKNESS UNDER PAVEMENTS, WALKS, AND STRUCTURAL FILLS
4 of 9
SHALL BE 12 INCHES. HAND OPERATED COMPACTION FILLS SHALL NOT EXCEED 6 INCHES.
SHEET No:
PROOF ROLLING - THE OWNER'S REPRESENTATIVE MAY REQUEST A PROOF ROLL (I.E. LOADED TEN
1764-25
WHEELER) OF SUBGRADE AREAS PRIOR TO PLACEMENT OF SUBBASE MATERIALS. AREAS THAT "FAIL" SHALL BE REMOVED AND REPLACED TO ACHIEVE A PASSING SUBGRADE.
JOB No:
C3.0 DRAWING No:
COBBLESTONE PLACE PHASE 2
NORTH
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
www.marathoneng.com
PROJECT PROPERTY LINE STORM SEWER, MANHOLE & FIELD/DROP INLET CENTERLINE OF SWALE GRADING LIMITS WETLANDS FLOODPLAIN
PROPOSED MAJOR CONTOUR PROPOSED MINOR CONTOUR DRAINAGE FLOW ARROW EXISTING SPOT ELEVATION PROPOSED SPOT ELEVATION EXISTING POWER POLE EXISTING TREE LINE TREE LINE / CLEARING LIMITS EROSION CONTROL MAT DROP INLET PROTECTION
FINALfor SITE PLANS
EXISTING CONTOUR
STATE OFNEW YORK
ADJACENT PROPERTY LINE
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE
BY
TOWN OF WEBSTER
CENTERLINE AND STATIONING
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
1025 RAVENSIDE LANE MONROECOUNTY
LEGEND:
1764-25 1"=30' RLB RPB 05/13/2025 REVISION
8/1/25 12/23/25 02/17/26
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS
07/06/26
JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
ROBERT P. BRINGLEY
DRAWING TITLE:
POND PLAN
5 of 9 SHEET No:
C3.1
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
LEGEND:
NORTH
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
2 UF
1 JS
4 SA
3 AR 6 BL
8 SA
3 GS
3 AR
2 PN 3 PA
6 IP 8 RG 2 PL 2 MS
3 BH
2 JC
6 PS
4 BL
6 BL
LIGHT BASE 2 SA
2 JC 5 BL
3 MC
2 JS
3 SA
TOWN OF WEBSTER
1 GS
FINALfor SITE PLANS
5 BL
1025 RAVENSIDE LANE MONROECOUNTY
1 QB
STATE OFNEW YORK
www.marathoneng.com
1 QB
3 BH
3 PG
3 PA
2 UP
SCALE: DRAWN: DESIGNED: DATE: REVISIONS
4 PG
DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
BY
1764-25 1"=30' RLB RPB 05/13/2025 REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
LIGHTING SCHEDULE Index
Manufacturer
Article name
Item number
Fitting
Luminous flux
Light loss factor
L1
Global Lighting Perspectives
AB40 SERIES
AB40AC-CL/G3L ED65-T5-27K
1x
7589 lm
0.80
Connected load Mounting Height 67.3 W
20'
Quantity 8
DECIDUOUS PLANTINGS
COPYRIGHT ã 2026 MARATHON ENG.
LANDSCAPING SCHEDULE KEY
BOTANICAL NAME
COMMON NAME
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
QTY.
SIZE
ROOT
AR
ACER RUBRUM 'MAGNIFICENT MAGENTA'
BURGUNDY BELLE RED MAPLE
6
TBD
BALLED & BURLAPPED
BL
BERBERIS WORRYFREE LEMONCUTIE
LEMON CUTIE BARBERRY
26
18" HT
2" CONT.
BH
BETULA NIGRA HERITAGE
HERITAGE BLUEBIRCH
6
10' HT
BALLED & BURLAPPED
GS
GLEDITSIA TRIA. INER. 'STREET KEEPER'
STREET KEEPER HONEYLOCUST
4
1 3/4" CALIPER
BALLED & BURLAPPED
IP
ILEX MERS. 'BLUE PRINCE & PRINCESS'
BLUE PRINCE(2) BLUE PRINCESS (4) HOLLY
6
24" HT
#5 CONT.
JC
JUNIPERUS SAB. 'CALGARY CARPET'
CALGARY CARPET JUNIPER
4
15-18" SPREAD.
#3 CONTAINER
JS
JUNIPERUS CHINENSIS 'SEA GREEN'
SEA GREEN JUNIPER
3
24" SPREAD
BALLED & BURLAPPED
MC
MALUS 'CARDINAL'
CARDINAL CRABAPPLE
3
2" CAL
BALLED & BURLAPPED
MS
MALUS 'SPRING SNOW'
SPRING SNOW CRABAPPLE
2
1 3/4" CALIPER
BALLED & BURLAPPED
PL
PHYSOCARPUS OPUL. 'LEMON CANDY'
LEMON CANDY NINEBARK
2
18-24" HT
BALLED & BURLAPPED
PS
PHYSOCARPUS OPUL. 'SUMMER WINE'
SUMMER WINE NINEBARK
6
3-4' HEIGHT
BALLED & BURLAPPED
PA
PICEA ABIES
NORWAY SPRUCE
6
6'-7' HEIGHT
BALLED & BURLAPPED
PN
PICEA A. NIDIFORMIS
BIRDS NEST SPRUCE
2
CLUMP
#2 CONTAINER
PG
PICEA GLAUCA
WHITE SPRUCE
7
6'-7' HEIGHT
BALLED & BURLAPPED
QB
QUERCUS BILOBA
SWAMP WHITE OAK
2
2-2.5" CALIPER
BALLED & BURLAPPED
RG
RHUS AROM. 'GRO-LOW'
GRO-LOW SUMAC
8
18" SPR
#2 CONTAINER
UF
ULMIS X. 'FRONTIER'
FRONTEIR ELM
2
2" CAL
BALLED & BURLAPPED
REMARKS
CLUMP FORM 3 STEM
GROUND COVER PLANTINGS ROBERT P. BRINGLEY
DRAWING TITLE:
LIGHTING & LANDSCAPING PLAN
FULL BODY
6 of 9
SHRUB PLANTINGS
SHEET No:
C4.0
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
£
DROP/ FIELD INLET
A
STONE EDGE TREATMENT (WITHOUT CURB)
A
TOWN OF WEBSTER
PAVEMENT SECTION
CONCRETE SIDEWALK
1025 RAVENSIDE LANE MONROECOUNTY
SANITARY TRENCH
FINALfor SITE PLANS
>
STATE OFNEW YORK
www.marathoneng.com
PAVEMENT MATCH
CONNECT TO EXISTING STORM STRUCTURE JOB NO: SCALE: DRAWN: DESIGNED: DATE: REVISIONS
CONCRETE CURB WITH SIDEWALK BEHIND £ <
£ <
DATE
STORM TRENCH PERFORATED PIPE
6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
BY
1764-25 AS SHOWN RLB RPB 05/13/2025 REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
RESERVED PARKING AND SIGNAGE TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
TOP VIEW
CONCRETE CURB WITH LAWN/ PLANTER BEHIND ROBERT P. BRINGLEY
DRAWING TITLE:
CONSTRUCTION DETAILS
FRONT VIEW
CONCRETE PAVEMENT
BIKE RACK DETAIL (TYP.)
SIDE VIEW
TALL CONCRETE CURB
7 of 9 SHEET No:
C5.0
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
3'
5:1
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
A D
B C D
DUMPSTER ENCLOSER
SCALE: DRAWN: DESIGNED: DATE: REVISIONS
STONE LINED EMERGENCY SPILLWAY ACCESS RAMP
RIPRAP OUTLET PROTECTION
DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
BY
TOWN OF WEBSTER
SILT FENCE
1025 RAVENSIDE LANE MONROECOUNTY
STABILIZED CONSTRUCTION ENTRANCE
FINALfor SITE PLANS
STOCKPILE AREA
STATE OFNEW YORK
www.marathoneng.com
1764-25 AS SHOWN RLB RPB 05/13/2025 REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
X
X
X
X
X
X
X X
X
X
X
X
X
X X
X
X
X
X
X
X
X X X X XX X X X X X X X X X XX
X
X X X X X
ROBERT P. BRINGLEY
BIORETENTION SECTION DETAIL DRAWING TITLE:
CONSTRUCTION DETAILS
EROSION CONTROL BLANKET SEDIMENT BASKET INLET PROTECTION
8 of 9
CONCRETE WASHOUT
SHEET No:
C5.1
1764-25 JOB No:
DRAWING No:
COBBLESTONE PLACE PHASE 2
3. PUBLIC WATER (MCWA AND MCHD)
3.1 SPECIFICATIONS - WATER MAINS AND APPURTENANCES TO BE CONSTRUCTED IN ACCORDANCE WITH THE REGULATIONS AND SPECIFICATIONS OF THE WATER AUTHORITY.
3.2 MATERIAL: · WATER MAIN(S) SHALL BE 6"-INCH, ZINC-COATED, CEMENT-LINED, CLASS 52 DUCTILE IRON PIPE. · WATER METER(S) SHALL BE LOCATED ON THE INTERIOR OF EXTERIOR WALLS IMMEDIATELY UPON SERVICE ENTRANCE INTO THE BUILDING(S). ON METERED SERVICES REQUIRING A 1 1/2-INCH OR LARGER METER A BYPASS AROUND THE METER IS REQUIRED. · ALL GATE VALVES SHALL HAVE STAINLESS STEEL BODY AND BONNET BOLTS.
ROCHESTER LOCATION
39 CASCADE DRIVE ROCHESTER, NY 14614 5 8 5 - 4 5 8 - 7 7 7 0 ITHACA LOCATION
3.3 TESTS:
SPECIFICATIONS. A WATER AUTHORITY REPRESENTATIVE MUST WITNESS THIS TEST.
· HEALTH SAMPLE - THE WATER MAIN SHALL BE DISINFECTED EQUAL TO AWWA STANDARD SPECIFICATIONS, DESIGNATION C-651, BY USING THE CONTINUOUS FEED METHOD. AFTER FLUSHING AND DISINFECTING THE WATER MAIN, WATER SAMPLES SHALL BE COLLECTED FROM THE MAIN BY THE HEALTH DEPARTMENT WITH JURISDICTION OF THE AREA. FIRE HYDRANTS ARE NOT ACCEPTABLE SAMPLING POINTS. APPROVAL AND NOTIFICATION BY THE HEALTH DEPARTMENT MUST BE RECEIVED BEFORE THE MAIN IS PLACED IN SERVICE.
· WATER MAINS AND ALL WATER SERVICE LINES SHALL HAVE A MINIMUM OF FIVE FEET OF COVER FROM FINISHED GRADE IN LAWN AREAS AND A MINIMUM OF SIX FEET OF COVER FROM FINISHED GRADE IN PAVED AREAS.
· MINIMUM VERTICAL SEPARATION BETWEEN WATER MAIN AND SEWER MAINS SHALL BE 18” MEASURED FROM THE OUTSIDE OF THE PIPES AT THE POINT OF CROSSING. MINIMUM HORIZONTAL SEPARATION BETWEEN WATER MAINS AND SEWER MAINS SHALL BE TEN FEET MEASURED FROM THE OUTSIDE OF THE PIPES. ONE FULL LENGTH OF WATER MAIN SHALL BE CENTERED UNDER OR OVER THE SEWER SO THAT BOTH JOINTS WILL BE AS FAR FROM THE SEWER AS POSSIBLE. WHERE A WATER MAIN CROSSES UNDER A SEWER, ADEQUATE STRUCTURAL SUPPORT (COMPACTED SELECTED FILL) SHALL BE PROVIDED FOR THE SEWERS TO PREVENT EXCESSIVE DEFLECTION OF JOINTS AND SETTLING ON AND BREAKING THE WATER MAINS.
· FIRE HYDRANT WEEP HOLES (DRAINS) SHALL BE PLUGGED WHEN GROUND WATER IS ENCOUNTERED WITHIN SEVEN FEET OF THE FINISHED GRADE.
· ALL MECHANICAL JOINT FITTINGS (TEES, BENDS, PLUGS, ETC.) SHALL BE BACKED WITH 2500 PSI CONCRETE THRUST BLOCKS OF APPROPRIATE SIZE TO PROVIDE THRUST RESTRAINT.
3.5 FLUSHING - WATER MAINS DESIGNATION C651 (LATEST REVISION). FOLLOWING DISINFECTION, THE WATER MAIN SHALL BE FLUSHED UNTIL THE CHLORINE CONCENTRATION IN THE WATER LEAVING THE MAIN IS NO HIGHER THAN THAT GENERALLY PREVAILING IN THE SYSTEM.
3.6 DISINFECTION - THE WATER MAIN PIPELINE SHALL BE DISINFECTED EQUAL TO AWWA STANDARD FOR DISINFECTING WATER MAINS DESIGNATION C651 (LAST REVISED). FOLLOWING DISINFECTION, THE WATER MAIN PIPELINE SHALL BE FLUSHED UNTIL THE CHLORINE CONCENTRATION IN THE WATER LEAVING THE MAIN IS NO HIGHER THAN THAT GENERALLY PREVAILING IN THE SYSTEM.
· ALL WATER MAIN FITTINGS NOT RECEIVING 24-HOUR CHLORINE DISINFECTION CONTACT TIME MUST BE SWAB DISINFECTED 30 MINUTES PRIOR TO INSTALLATION.
3.7 SAMPLING - THE SAMPLING POINT(S) MUST BE DECONTAMINATED BY FLAMING. · FIRE HYDRANTS ARE NOT ACCEPTABLE SAMPLING POINTS.
FINALfor SITE PLANS
3.4 INSTALLATION:
STATE OFNEW YORK
· PRESSURE - WATER MAINS TO BE PRESSURE TESTED IN ACCORDANCE WITH THE LATEST WATER AUTHORITY
SOIL BEARING STRENGTH - 1,000 PSF 100 PSI TEST PRESSURE
SOIL BEARING STRENGTH - 1,000 PSF 100 PSI TEST PRESSURE
www.marathoneng.com
· THE MONROE COUNTY DEPARTMENT OF PUBLIC HEALTH MUST RECEIVE AT LEAST 48-HOUR ADVANCE NOTIFICATION REQUESTING SAMPLING SERVICES. SAMPLING WILL NOT BE PERFORMED PRIOR TO RECEIPT FROM A NEW YORK STATE LICENSED OR REGISTERED DESIGN PROFESSIONAL (ENGINEER, ARCHITECT OR LAND SURVEYOR WITH A SPECIAL EXEMPTION UNDER SECTION 7208(N) OF THE EDUCATION LAW) CERTIFYING THAT THE WATER SUPPLY IMPROVEMENTS, TESTING AND DISINFECTION PROCEDURES WERE COMPLETED IN ACCORDANCE WITH THE APPROVED PLANS, REPORTS, SPECIFICATIONS AND ANY APPROVED AMENDMENTS. THE DEPARTMENT WILL COLLECT SAMPLES FOR FREE CHLORINE RESIDUAL, TOTAL COLIFORM, ESCHERICHIA COLI (E. COLI) AND TURBIDITY.
· THE WATER MAIN SHALL NOT BE PLACED INTO SERVICE UNTIL SO AUTHORIZED BY THE MONROE COUNTY DEPARTMENT OF PUBLIC HEALTH.
3.8 SEPARATION - MINIMUM VERTICAL SEPARATION BETWEEN WATER MAIN PIPELINES AND SEWER PIPELINES SHALL BE 18 INCHES MEASURED FROM THE OUTSIDE OF THE PIPES AT THE POINT OF CROSSING. ONE FULL STANDARD LAYING LENGTH OF WATER MAIN SHALL BE CENTERED UNDER OR OVER THE SEWER SO THAT BOTH JOINTS WILL BE AS FAR FROM THE SEWER AS POSSIBLE. IN ADDITION, WHEN THE WATER MAIN PASSES UNDER A SEWER, ADEQUATE STRUCTURAL SUPPORT (COMPACTED SELECTED FILL) SHALL BE PROVIDED FOR THE SEWER TO PREVENT EXCESSIVE DEFLECTION OF JOINTS AND SETTLING OF THE SEWER ON THE WATER MAIN. MINIMUM HORIZONTAL SEPARATION BETWEEN PARALLEL WATER MAINS AND SEWER PIPES (INCLUDING MANHOLES AND VAULTS) SHALL BE 10' MEASURED FROM THE OUTSIDE OF THE PIPES, MANHOLES OR VAULTS.
TOWN OF WEBSTER
POLYETHYLENE ENCASEMENT PER ANSI/AWWS C105/AZ1.5-82 PRIOR TO WATER MAIN INSTALLATION. SOIL TESTING SHALL BE CONDUCTED BY AN APPROVED SOIL TESTING LABORATORY IN ACCORDANCE WITH WATER AUTHORITY STANDARDS.
8 40 H AN SH AW RD , ST E 6 ITHACA, NY 14850 6 0 7 - 2 4 1 - 2 9 1 7
1025 RAVENSIDE LANE MONROECOUNTY
· SOIL - THE CONTRACTOR SHALL PROVIDE A SOIL TEST EVALUATION TO DETERMINE THE NEED FOR
3.9 HYDRANTS - WHEN INSTALLING FIRE HYDRANTS, SHOULD GROUND WATER BE ENCOUNTERED WITHIN SEVEN FEET (7') OF THE FINISHED GRADE, FIRE HYDRANT WEEP HOLES (DRAINS) SHALL BE PLUGGED.
VERTICAL DOWN THRUST BLOCKS
3.10 TESTING - THE WATER MAIN PIPELINE AND APPURTENANCES SHALL BE PRESSURE/LEAKAGE TESTED IN ACCORDANCE WITH THE MINIMUM REQUIREMENTS OF THE AWWA STANDARD C600 (LATEST VERSION) OR IN ACCORDANCE WITH MORE STRINGENT REQUIREMENTS IMPOSED BY THE SUPPLIER OF WATER.
MCWA STANDARD DETAIL (DME 7, JAN 2025) NTS
MCWA 4" AND LARGER WATER SERVICE LINE NOTES (DME 26, JAN 2025) 1.
ALL MATERIALS, INSTALLATION AND TESTING PROCEDURES SHALL BE IN COMPLIANCE WITH CURRENT AWWA STANDARDS AND IN ACCORDANCE WITH THE REGULATIONS AND SPECIFICATIONS OF THE AUTHORITY. SHOULD A CONFLICT EXIST THE AUTHORITY’S SPECIFICATIONS SHALL GOVERN.
2.
WATER SERVICE LINES SHALL HAVE A MINIMUM OF FIVE FEET OF COVER FROM FINISHED GRADE IN NONPAVEMENT AREAS AND SIX FEET OF COVER FROM FINISHED GRADE IN PAVED AREAS.
3.
WATER SERVICE LINES SHALL BE SEPARATED AT LEAST TEN FEET, MEASURED FROM THE OUTSIDE OF THE PIPES, FROM SEWER MAINS OR SEPTIC SYSTEMS.
4.
WATER SERVICE LINES SHALL BE IDENTIFIED AS:
HORIZONTAL & VERTICAL UP THRUST BLOCKS
FROM THE WATER MAIN TO AND INCLUDING THE CONTROL VALVE ON THE ROW/PROPERTY/EASEMENT LINE
6"
ZINC COATED CLASS 52 D.I.P.*
CMB
MCWA STANDARD DETAIL (DME 6, JAN 2025) NTS
FROM THE CONTROL VALVE TO THE METER
6"
D.I.P.*
CMB
(a) ACCEPTABLE MATERIALS IS *CLASS 52 CEMENT MORTAR LINED ZINC-COATED DUCTILE IRON PIPE. (b) SERVICE TYPES INCLUDE: DOMESTIC = DS, FIRE = FS, OR COMBINE = CMB 5.
THE WATER AUTHORITY’S PORTION OF THE WATER SERVICE LINE SHALL BE INSTALLED PRIOR TO THE PRIVATE PORTION OF THE SERVICE LINE.
6.
WATER METER(S) TO BE LOCATED ON THE INTERIOR OF EXTERIOR WALLS(S) IMMEDIATELY UPON SERVICE ENTRANCE INTO THE BUILDING FOOTPRINT OR HEATED ENCLOSURE. A BYPASS ASSEMBLY IS NOT REQUIRED AROUND 5/8-INCH THROUGH 1-INCH METERS. 1 ½-INCH AND 2-INCH METERS MAY REQUIRE A BYPASS ASSEMBLY DEPENDING UPON THE APPLICATION. 3-INCH AND LARGER METERS REQUIRE A BYPASS ASSEMBLY.
7.
WATER SERVICE LINES SIZED 4-INCHES OR GREATER SHALL BE:
SCALE: DRAWN: DESIGNED: DATE: REVISIONS DATE 6/17/25 7/15/25 12/23/25 02/17/26 07/06/26
BY
1764-25 1"=30' RLB RPB 05/13/2025 REVISION
JPC TOWN COMMENTS JPC TOWN COMMENTS JPC TOWN COMMENTS JPC MCDOH COMMENTS JPC ISSUED MYLAR
TI SIO NIATLOIV FO E W N KR O Y ETATS O NITA D UE C W A L ELCITRA ,541O NITCES 9027 R OF N Y A ,OSNREP SSELU N N GITCA RU EN D EHTO NITCERID FO DESA NECIL LO NISSEFO A RP REENIN GE ON R DL ,R A O YEVR US O T RETLA NI Y N A ,W YA N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL .R A O YEVR US FI N AM ETI N GIRAEB EHT LAES FO A LO NISSEFO A RP REENIN GE ON R DL R A O YEVR US S,IDERETLA EHTN GIRETLA REENIN GE O R N DL R A O YEVR US LLA HS XIFFA O T EHT M ETI RIEHT LAES N D EHT O A NITA NT O DERETLA" "YB OLD W ELOF YBRIEHT ER UTG NIS A N D EHT ETA A D FO H US ,O C NITARETLA N D CIFIACEPS A .O NITARETLAEHT FOO NITPIRCSED
COPYRIGHT ã 2026 MARATHON ENG.
· H PRESSURE TESTED IN ACCORDANCE WITH THE LATEST SPECIFICATIONS OF THE MONROE COUNTY WATER AUTHORITY. A WATER AUTHORITY REPRESENTATIVE MUST WITNESS THIS TEST.
VALVE MCWA STANDARD DETAIL (DME 5, JAN 2025) NTS
DISINFECTION/ BLOW-OFF/ SAMPLING TAP (TEMPORARY) MCWA STANDARD DETAIL (DME 14, JAN 2025) NTS
· DISINFECTED BY USING THE CONTINUOUS FEED METHOD ACCORDING TO AWWA STANDARD SPECIFICATIONS. AFTER FLUSHING AND DISINFECTING THE SERVICE LINE, WATER SAMPLES SHALL BE COLLECTED IN ACCORDANCE WITH THE DEPARTMENT OF HEALTH THAT HAS JURISDICTION OF THE AREAS REQUIREMENTS. APPROVAL AND NOTIFICATION BY THE HEALTH DEPARTMENT OF PASSING HEALTH SAMPLE TEST(S) MUST BE RECEIVED BEFORE THE SERVICE WILL BE ACTIVATED BY THE WATER AUTHORITY.
ROBERT P. BRINGLEY
DRAWING TITLE:
CONSTRUCTION DETAILS
9 of 9
DIP TRENCH MCWA STANDARD DETAIL (DME 3, JAN 2025) NTS
SHEET No:
C5.2
1764-25 JOB No:
DRAWING No: