Planning Board Meeting
Planning Attachment 2024.08.06

Building Plans

August 6, 2024 · 87 min read · extracted text · View original
REVISION

00

THE HUMAN BEAN JOB NAME

CORP PLAN SET

PRELIMINARY USE ONLY

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 1 of 54

CUSTOMER:

PLAN SET:

13'6" x 45' PLANS

NOTES

Drawing Scale: Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING JOB SHEET

1

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30. 31. 32. 33. 34. 35. 36. 37. 38. 39. 40. 41. 42. 43. 44. 45. 46. 47. 48. 49. 50. 51. 52. 53. 54. 55. 56. 57. 58. 59.

NOTES

3-1 REFER TO ENGINEERING PRINTS FOR REBAR DETAILS Drawing Scale: Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING COVER SHEET

PRELIMINARY USE ONLY

JOB SHEET COVER SHEET FOUNDATION PLAN STEEL PLAN FLOOR JOIST LAYOUT CEILING JOIST LAYOUT FRAMING PLAN - PLAN VIEW FRAMING PLAN - FRONT ELEVATION FRAMING PLAN - LEFT ELEVATION FRAMING PLAN - RIGHT ELEVATION FRAMING PLAN - REAR ELEVATION FLOOR PLAN W DIMENSIONS EQUIPMENT LAYOUT PLAN EQUIPMENT SCHEDULE MECHANICAL PLAN ELECTRICAL PLAN- PLAN VIEW ELECTRICAL PLAN - ROOF PLAN VIEW LIGHTING PLAN - PLAN VIEW ELECTRICAL PLAN - FRONT INTERIOR ELEVATION ELECTRICAL PLAN - RIGHT INTERIOR ELEVATION ELECTRICAL PLAN - REAR INTERIOR ELEVATION ELECTRICAL PLAN - LEFT INTERIOR ELEVATION ELECTRICAL PLAN - AUXILIARY ELEVATIONS ELECTRICAL PLAN - PANEL AND EQUIPMENT SCHEDULE ELECTRICAL PLAN - LOW VOLTAGE PLUMBING PLAN - WATER PLUMBING PLAN - WATER ELEVATIONS PLUMBING PLAN - DWV PLUMBING PLAN - ROOF DRAINS FRONT ELEVATION - SLOPED FRONT ELEVATION - PARAPET REAR ELEVATION - SLOPED REAR ELEVATION - PARAPET RIGHT SIDE ELEVATION - SLOPED RIGHT SIDE ELEVATION - PARAPET LEFT SIDE ELEVATION - SLOPED LEFT SIDE ELEVATION - PARAPET FRONT INTERIOR ELEVATION REAR INTERIOR ELEVATION RIGHT SIDE INTERIOR ELEVATION LEFT SIDE INTERIOR ELEVATION CROSS SECTION OF BUILDING 1 ENERGY ENVELOPE DETAILS INTERIOR ELEVATIONS OF BATHROOM SLEEPER DETAILS PARAPET OPENING DETAILS & ROOF ACCESS LARGE PARAPET SMALL PARAPET PARAPET WALLS AWNINGS AND STANCHION DETAILS COUNTERTOP / CABINET ARRANGEMENT BUILDING COLOR SPECIFICATIONS WALK-IN COOLER SPECIFICATIONS WALK-IN COOLER SPECIFICATIONS INTERIOR IMAGES MENU BOARD CONDUIT SPECS MENU BOARD PLACEMENT SPECS DRIVE THRU WINDOW SPECS LOW VOLTAGE RACK

2

00r 10-12-21 00 03-04-21 REV DATE

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 2 of 54

COVER SHEET

EDK EDK BY APPROVAL

KNOCKOUT MOVED TO FOLLOW METER BASE CONDUIT, METER BASE MOVED TOWARD DOOR PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

FOUNDATION TYPES

Local engineered stem wall / pier foundation required for modular building applications. Local engineering required for slab on grade applications.

ROLL FROM THIS END, FACE UP

2'-0"

2.

11 15'-2 16 "

FOUNDATION

11 12'-6 16 "

8"

11 43'-2 16 "

3'-10"

2'-0"

2'-6"

KNOCKOUT FOR POWER

KNOCKOUT FOR DWV 1'-4"

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

1.

11 45-10 16 "

1'-0" 1'-4"

NOTES

3-1 REFER TO ENGINEERING PRINTS FOR REBAR DETAILS Drawing Scale: Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FOUNDATION PLAN

PRELIMINARY USE ONLY

3

00r 10-12-21 00 03-04-21 REV DATE

EDK EDK BY APPROVAL

KNOCKOUT MOVED TO FOLLOW METER BASE CONDUIT, METER BASE MOVED TOWARD DOOR PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

BOM DESCRIPTION LBS LENGTH TYPE MATERIAL 3/16" PLATE 6 1/2" 6 SIDE WALL STEEL TO STRETCHER 90° BRACE Plain Carbon Steel 1.1 Plain Carbon Steel 142.1 13'-6 5/16" FRONT WALL C-CHANNEL MC12x10.6 1 Plain Carbon Steel 118.4 13'-6 5/16" 3 CROSS TUBE BRACES TR4x2x0.25 10 ALL-THREAD HOLDDOWN SPACER TS1.25x1.25x0.180 Plain Carbon Steel 0.8 4" 10 3/4" CORNER BRACE L3x3x0.25 Plain Carbon Steel 4.3 4 Plain Carbon Steel 453.9 44'-2 5/16" PASSANGER SIDE WALL C-CHANNEL MC12x10.6 1 44'-2 5/16" DRIVER SIDE WALL C-CHANNEL MC12x10.6 Plain Carbon Steel 1 5/8"-11NC ALL-THREAD HOLDDOWN 5/8"-11 THREADED ROD Plain Carbon Steel 0.9 10 10" 3/16" EXPANDED STEEL Plain Carbon Steel 0.8 8 FOUNDATION VENT COVER 1'-0" 13'-6 5/16" MC12x10.6 Plain Carbon Steel 1

1'-0" TYP 10 34"

1"

6 21"

SIDE WALL STEEL TO STRETCHER 90° BRACE (OPTIONAL) 3/16" PLATE 11 44'- 216 "

35'-4"

32'-1041"

32'-221" FRONT OF CUTOUT 32-534"

30'-0"

27'-4"

24'-221" FRONT OF CUTOUT

22'-0"

19'-4"

16'10 41"

16'-5 34"

16'-221" FRONT OF CUTOUT

1

1" 2 41"

1'-0"

J

2 41"

K

MESH WELDED TO INSIDE OF STEEL FRAME MEMBERS

DETAIL J SCALE 1 : 8 2 41"

1 2" ALL TOP HOLES 3 4" ALL BOTTOM HOLES

16'-8" RIM BOARD BREAK 32'-8" RIM BOARD BREAK

6

8

ROLL FROM THIS END, FACE UP

6 21" 2 41"

FOUNDATION VENT COVER 3/16" EXPANDED STEEL

11 43' - 216 "

9

40'-8"

CORNER BRACE L3x3x0.25

1 2"

5

14'-0"

11'-4"

8'-221" FRONT OF CUTOUT 8'-8"

6'-0"

3'-4"

1'-0"

9'- 21" TYP

3" CUTOUT TYP.

0"

"

2

1

4" TYP

9

CUTOUTS FOR CRAWL SPACE VENTING (EACH SIDE)

8 1

2"

38'-4"

11" CUTOUT TYP.

5'- 41"

1"

3'- 34" TYP

1 2 3 4 5 6 7 8 9 10

1 2"

LL 13'- 158"

11 12'-916 "

11'-581"

10 1

6"

TYPICAL DETAIL K SCALE 1 : 8

11 13'-616 "

2

FRONT

REAR

3 8

5/8"-11 N.C. ALL-THREAD

541"

7

10"

10 34"

1 1/4" X 1 1/4" X .180" SQUARE TUBING

2'-1 58" 5 8"

9"

581" 11 44'-2 16

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING STEEL PLAN

PRELIMINARY USE ONLY

4

44'- 15 16"

33'-11 15 16" FRONT OF OPTIONAL BRACKETS (BOTH SIDES)

33'-10" FRONT OF TUBE

26'- 11 78" TIEDOWN (BOTH SIDES)

20'- 7 15 16 " FRONT OF OPTIONAL BRACKETS (BOTH SIDES)

CORNER BRACE POSITIONING

20'-6" FRONT OF TUBE

QTY

10 SETS

11'-0" TIEDOWN (BOTH SIDES)

SECTION L-L SCALE 1 : 12

11 9'- 11 16 " FRONT OF OPTIONAL BRACKETS (BOTH SIDES)

4

9'-10" FRONT OF TUBE

4" 1 34 "

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

ITEM NO. QTY.

REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

3 21" 3 4"

5 33'-11 16 "

CORNER CUTOUTS 2X8 P.T. RIM BOARD

5 20'-7 16 " 5 9'-11 16 "

DOUBLE BCIs FOR WALK-IN COOLER

10'-7"

13'-3"

3 21"

2X8 RIM BOARD (INSIDE C-CHANNEL 2"

9 9' 1016 "

DETAIL M SCALE 1 : 5 TYPICAL 4 CORNERS

N

10' 1 41"

2'-4" CRAWL SPACE R.O.

M

3" 2 41"

REAR

DETAIL Q SCALE 1 : 5 TYPICAL CUTOUT AT EACH TIEDOWN CENTERED ON TIEDOWN ROUTERED OR CUT SLOT FOR EXPANDED METAL ON OUTSIDE OF 2X8 P.T.

9 7'- 16 " FROM FACE OF STEEL, HEADOUT FOR CRAWL SPACE

FRONT

3 16" TYP FROM FACE

OF STEEL TO FACE OF RIM JOIST

8"

1'-4" TYP

11 1'-6 16 " FROM FACE OF STEEL TO CNTR LAST BCI

2'-6" FROM FACE OF STEEL, HEADOUT FOR FLOOR SINK

2'-0" FROM FACE OF STEEL TO CNTR LAST BCI

1 2"

23'-11" DOUBLER 32'-1" DOUBLER

FRAMER, THESE NUMBERS ARE FROM FRONT OR BACK OF STEEL.

5 44'-2 16 "

5 33'-11 16 "

5 32'-2 16 "

9 26'-11 16 "

5 16'-2 16 "

10'-11 58"

5 9'-11 16 "

0"

5 24'-2 16 "

P

Q

3 4"

1 34"

11"

THESE (3) HATCHED AREAS ARE CUT-OUT ONLY IF THE GUSSET BRACES HAVE BEEN INSTALLED.

3X 1"

5 8'-2 16 "

3 4"

1'-10 13 16"

5 20'-7 16 "

DETAIL N SCALE 1 : 5 TYPICAL AT EACH VENT

ROLL FROM THIS END, FACE UP

9 1/2" ROSEBURG 400 RFPI TYP.

3 4"

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

R30 BATT INSULATION TYP.

ALL (4) OF THESE DIMENSIONS ARE VALID ONLY IF GUSSETS HAVE BEEN INSTALLED AND ARE MEASUREMENTS OF WOOD ONLY.

FRAMER, THESE NUMBERS ARE MEASURED ON 2X8 P.T., NOT STEEL 16'-0" 2X8 P.T. BREAK

32'-0" 2X8 P.T. BREAK

DETAIL P SCALE 1 : 5 TYPICAL AT EACH VENT

NOTES:

LEGEND

6 MIL. SHALL BE INSTALLED. INSULATION BATT SHALL BE INSTALLED BETWEEN FLOOR JOISTS INSULATION BAFFLES TO BE INSTALLED PER CODE AT FOUNDATION VENTS NOTED ON STEEL PLAN.

• • •

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

ROLL FROM THIS END, FACE UP

3 4"

REVISION

00

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FLOOR JOIST LAYOUT

PRELIMINARY USE ONLY

FRAMING DIRECTION

5

00q 08-26-21 EDK 00 03-04-21 EDK BY APPROVAL REV DATE

KNOCKOUT ADDED FOR WALKIN SINK, DOUBLE JOIST MOVED TO PROPER LOCATION PRELIMINARY COPY

REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

RIM BOARD DOUBLER AT RIM BOARD BREAK

SEE ENGINEERING DRAWINGS FOR LVL HEADERS AT CEILING JOIST HEIGHT

4'-0" 24'-0" RIM BOARD BREAK

1.4E RIDGERIM LVL RIMBOARD 2X10 BLOCKING (2 BAYS DEEP) AT PANEL EDGES W PLYWOOD INFILL ON BCIs FOR BRACING (REFERENCE ENGINEERING DRAWINGS FOR SPECIFIC REQUIREMENTS)

4'-0"

2 X 2'-5 38"

2 X 5'-5 38"

4'- 38"

2'-0"

2x4 BLOCKING FOR DROP CEILING

R REAR

R

2x4 BLOCKING FOR DROP CEILING

2 X 2'-5 38"

1'-6 38"

2 X 5'-5 38"

4'-0"

FRONT

R30 BATT INSULATION TYP.

1'-4" TYP

1'-4"

11 13'-6 16 "

2x4 BLOCKING FOR DROP CEILING

10'-6 78"

22'-9 13 16"

9 1/2" ROSEBURG 400 RFPI TYP.

DOUBLE BCI FOR PARAPET CROSS WALL

2x4 BLOCKING FOR ROOF DRAINS

27'-10 78"

2x4 BLOCKING FOR ROOF DRAINS

Angle =1/4" : 1'

SECTION R-R SCALE 1 : 12

LEGEND

NOTES

4 MIL. SHALL BE INSTALLED AGAINST INTERIOR SPACE SIDE OF CEILING JOISTS AS VAPOR BARRIER. INSULATION BATT SHALL BE INSTALLED BETWEEN CEILING JOISTS Drawing Scale: 0.25:12 THE HUMAN BEAN Plot Scale: 1:1 • •

Internal ID:

HBC-O6S

13'6" X 45' PREFABRICATED BUILDING CEILING JOIST LAYOUT

PRELIMINARY USE ONLY

9 416 " LOW SIDE OF ANGLED BLOCK

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

11 44'-2 16 "

FRAMING DIRECTION

6

PROJECT REVIEW

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP 3'-8"

BD

BD BE

5'-4 21"

11 7'-1 16 "

9'-6 21"

3'-0"

2X 1'-7 38"

ROLL FROM THIS END, FACE UP

2'-10 38"

5'-8"

BE

3'-2" R.O.

9 6'-1 16 "

BB

3 7'-5 16 "

3'-4 21" DOOR R.O.

3'- 21"

2X4 INTERIOR FRAMING 7'-10" R.O.

10'-8 38"

2'-10 38"

2X6 EXTERIOR FRAMING

11 13'-6 16 "

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

REVISION

00

2X 7'-10" R.O. 9'-5 38"

BB

3 33'-11 16 "

9 10'-3 16 "

11 44'-2 16 "

SECTIONS ON PAGE 12 (REAR ELEVATIONS)

NOTES

INSULATION IS BATT CUT BETWEEN STUDS. ALL LENGTHS ARE REFERENCE ONLY, AND WILL VARY BASED ON FINAL FRAMED WALL HEIGHT, MOISTURE IN LUMBER AND CONDITIONS ON SITE WHERE THE FRAMER MAY HAVE TO ALTER FRAMING TO ACHIEVE THE OVERALL DESIGN INTENT.

• •

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRAMING PLAN - PLAN VIEW

PRELIMINARY USE ONLY

LEGEND FRAMING DIRECTION

7

00s 10-21-21 EDK 00 03-04-21 EDK BY APPROVAL REV DATE

ADDED SECTIONS TO THE FRAMING PLAN VIEW FOR CLARITY OF BLOCKING PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

COMMON STUDS MAY BE SLIGHTLY OFF OF LAYOUT IF IT MAKES SENSE TO MOVE THEM OVER AND DOESN'T AFFECT EXTERIOR SHEATHING LAYOUT SUCH AS A STUD THAT IS ON THE EDGE OF AN EXTERIOR PANEL.

3.5"X7.5" VERSALAM

ROLL FROM THIS END, FACE UP

REVISION

00

HEADER FOR WINDOW OPENING IS IN ROOF SECTION ABOVE WALL, PORTAL FRAMED.

11 13'-6 16 "

ENSURE WHEN, OR IF, MOVING A STUD, THAT IT DOESN'T INTERFERE WITH A PLUMBING CHASE, ELECTRICAL CHASE OR LOW VOLTAGE CHASE AND THAT IT DOESN'T OBSCURE A TIEDOWN LOCATION.

5'-6" R.O.

(THIS NOTE APPLIES TO ALL VIEWS AND PAGES)

2X6 EXTERIOR FRAMING

1'-3 41" 2'-2 78" 2'-10 38"

ROLL FROM THIS END, FACE UP

3'-2" SILL HEIGHT

R21 BATT INSULATION BETWEEN STUDS

1'-4" TYP 7'-10" R.O. 10'-8 38" 1 12'-216 "

NOTES

BATT INSULATION TO BE CUT BETWEEN STUDS. ALL LENGTHS ARE REFERENCE ONLY, AND WILL VARY BASED ON FINAL FRAMED WALL HEIGHT, MOISTURE IN LUMBER AND CONDITIONS ON SITE WHERE THE FRAMER MAY HAVE TO ALTER FRAMING TO ACHIEVE THE OVERALL DESIGN INTENT.

• •

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRAMING PLAN - FRONT WALL ELEVATION

PRELIMINARY USE ONLY

LEGEND FRAMING DIRECTION

8

00 03-04-21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

R21 BATT INSULATION BETWEEN STUDS

ROLL FROM THIS END, FACE UP

TOP PLATE FROM REAR WALL

TOP PLATE FROM FRONT WALL

11 44'-2 16 "

9'-0"

5'-6" R.O.

1'-4"

3'-2"

2X6 EXTERIOR FRAMING

1'-4" TYP

EXTRA STUD FOR HOLD-DOWNS

BLOCKING FOR EXTERIOR SERVING TRAY 26'-4 34"

7'-10" R.O.

11 9 16 " 1'-1 13 16"

8'-11 13 16"

43'-3 58"

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

REVISION

00

NOTES

BATT INSULATION TO BE CUT BETWEEN STUDS. ALL LENGTHS ARE REFERENCE ONLY, AND WILL VARY BASED ON FINAL FRAMED WALL HEIGHT, MOISTURE IN LUMBER AND CONDITIONS ON SITE WHERE THE FRAMER MAY HAVE TO ALTER FRAMING TO ACHIEVE THE OVERALL DESIGN INTENT.

• •

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRAMING PLAN - LEFT WALL ELEVATION

PRELIMINARY USE ONLY

LEGEND FRAMING DIRECTION

9

00 03-04-21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

11 44'-2 16 "

TOP PLATE FROM FRONT WALL

BATHROOM WALL FRONT EDGE

2X6 EXTERIOR FRAMING

TOP PLATE FROM REAR WALL

9'-0" 5'-6" R.O.

1'-4" 2'-7"

11 9 16 "

1'-1 13 16"

1'-4" TYP 7'-10" R.O.

THIS BLOCKING IS ON THE INSIDE OF THE BATHROOM WALL (FOR ADA GRAB BARS)

EXTRA STUD FOR HOLD-DOWNS

8'-11 13 16" 10'-3 41" LOCATION TO BE VERIFIED BY FRAMER

2'-11" 4'-5"

10" TYP

3'-2"

BLOCKING FOR EXTERIOR SERVING TRAY

R21 BATT INSULATION BETWEEN STUDS

26'-3 41" LOCATION TO BE VERIFIED BY FRAMER 33'-5 58"

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

REVISION

00

NOTES

BATT INSULATION TO BE CUT BETWEEN STUDS. ALL LENGTHS ARE REFERENCE ONLY, AND WILL VARY BASED ON FINAL FRAMED WALL HEIGHT, MOISTURE IN LUMBER AND CONDITIONS ON SITE WHERE THE FRAMER MAY HAVE TO ALTER FRAMING TO ACHIEVE THE OVERALL DESIGN INTENT.

• •

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRAMING PLAN - RIGHT WALL ELEVATION

PRELIMINARY USE ONLY

LEGEND FRAMING DIRECTION

10

00 03-04-21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

R21 BATT INSULATION BETWEEN STUDS

R21 BATT INSULATION BETWEEN STUDS

2X6 EXTERIOR FRAMING

ELECTRICAL PANEL BLOCKING (VARIOUS CONFIGURATIONS)

11 13'-6 16 "

2X6 EXTERIOR FRAMING 11 13'-6 16 "

ROLL FROM THIS END, FACE UP

9'-0"

3'-0"

6'-10 21" R.O.

6'-10 21" R.O.

3'-0" TO CENTER

5'-5" 5'-6" TO CENTER

BLOCKING FOR SINK AND MIRROR

9'-0"

5'-6"

2X 10"

1'-8"

BLOCKING FOR WATER HEATER

1'-5 15 16"

1'-4" 11 7'-8 16 "

4'-1 15 16" 3'-4 21" R.O.

11 7'-1 16 "

3'- 21"

3'-4 21" R.O.

11 7'-1 16 "

11 13'-6 16 "

3'- 21"

11 13'-6 16 "

INSIDE BLOCKING AT BACK WALL

OUTSIDE BLOCKING AT BACK WALL BLOCKING FOR WATER HEATER

SECTION BB-BB IN BATHROOM LOOKING TOWARD FRONT OF BUILDING

NOTES:

SECTION BD-BD IN HALL WAY LOOKING TOWARD BATHROOM

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRAMING PLAN - REAR WALL ELEVATION

5'-5"

SECTION BE-BE IN BATHROOM LOOKING TOWARD HALLWAY

BATT INSULATION TO BE CUT BETWEEN STUDS. ALL LENGTHS ARE REFERENCE ONLY, AND WILL VARY BASED ON FINAL FRAMED WALL HEIGHT, MOISTURE IN LUMBER AND CONDITIONS ON SITE WHERE THE FRAMER MAY HAVE TO ALTER FRAMING TO ACHIEVE THE OVERALL DESIGN INTENT.

• •

4'-10"

7'-1"

10" 4'-0"

4'-0"

2'-6" 1'-6"

1'-10 41"

3'-0"

3'-0"

6'-0"

BLOCKING FOR MOP SINK WATER SUPPLY

ROLL FROM THIS END, FACE UP

BLOCKING FOR HALLWAY SINK

3'-0"

2X 10"

1'-8"

BLOCKING FOR ADA GRAB BAR BEHIND TOILET

LEGEND FRAMING DIRECTION ADDED SECTION VIEWS BB, BD, BE FOR CLARITY OF BLOCKING PRELIMINARY COPY

PRELIMINARY USE ONLY

11

REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00 7 19'-4 16 " FLOOR SINK MIDPLANE

3'-2 81"

2'-8 34"

CUSTOMER SUPPLIED DRY STORAGE AREA 1'-11 5/8" 4'-11 78" 4'-5 58"

UPPER SHELVING

1'-10 41"

5 10'-6 16 " OPENING 10'-2 58" WALK

6'-2 21"

16'-8 81"

1 9'-10 16 "

IN LENGTH

5 7'-5 16 "

2'-0"

BA

2'-0"

7 22'-8 16 " FLOOR SINK MIDPLANE 11 20'-4 16 " BOLLARDS

12'-6" BOLLARDS

3" GAP

UPPER SHELVING

1'-6"

1'-6"

3'-2 81"

6'-5 58"

9'-5 21" INSIDE 5'-3 21" INSIDE

3 2'-9 16 "

9 2'-11 16 "

3'-2"

3" GAP

5'-4" WALK IN WIDTH

UPPER SHELVING

15'- 58" 2'-6"

4'-6 81"

9 4'-4 16 "

2'-7" CLEAR SPACE

9'-10 78"

9 21"

UPPER SHELVING UPPER SHELVING

3'- 81"

3 3'-7 16 "

8'- 21"

1'- 21"

1'- 21"

12'-6 116 " FINISHED INSIDE

2 58"

7 5'-8 16 " FLOOR SINK MIDPLANE

BOLLARDS (BY OTHERS)

3 2'-9 16 "

7 4'-3 16 " FLOOR SINK MIDPLANE

13'-7 21" WITH SHEATHING

11 14'- 16 " BOLLARDS

2 58"

2 58" BOLLARDS 12'-6" BOLLARDS

11 43'-2 16 " FINISHED INSIDE

44'-3 21" WITH SHEATHING

BC

4'-8"

2'-6"

4'-6" 3'-4"

NOTES:

SINGLE USER TOILET ROOM SHALL BE PROVIDED WITH A PRIVACY LOCK AND OCCUPIED INDICATOR SECTION: 2019 OSCC 1209.3.1. ALL WINDOWS AND DOORS SHALL BE CAULKED TO SUBSIDING (FOR WINDOWS) AND LOW EXPANDING FOAM • WILL BE USED IN ALL CRACKS AND GAPS. "STORM WRAP" TAPE SHALL BE USED ON WINDOW FLANGES AND 7 78" DOOR JAMB-TO-WALL JOINTS. 6" MAX 8" MIN EXTERIOR OF BUILDING IS TO BE CEMENT PLASTER FINISH (AKA STUCCO). • 1'-5" MIN ADA DIMENSIONS AND CLEARANCES WALLS TO BE 1/2" DRYWALL AND FRP, CEILING TO BE T-BAR W TILE "DROP CEILING". • SECTION BB-BB F/E = FIRE EXTINGUISHER • SCALE 3/8" : 1' BATHROOM IS 1/2" DRYWALL AND FRP. • 00u 12/03/21 EDK Drawing Scale: 0.3125:12 00r - occupancy note added. THE HUMAN BEAN 00r 10/12/21 EDK (Plan Review: Page 2 Architectural Note 2) Plot Scale: 1:1 00 03/04/21 EDK •

Internal ID:

HBC-O6S

13'6" X 45' PREFABRICATED BUILDING FLOOR PLAN

PRELIMINARY USE ONLY

12

REV

DATE

2'-10" 3'-4"

4'-0"

2'-3" MIN

3'-8" 3'-4" 9" MIN

BC

1'-0" MAX

1'-6 21" 2'-10"

3'-6"

3'-4"

BB

00u - ADA clearance elevations added. (Plan Review2: Page 1 Architectural Note 1)

1'-6"

BB 1'-0" MIN

1'-6" MAX

5'-0"

3'-0" MIN 2'-0" MIN

5'-0" TURNING CIRCLE

ROLL FROM THIS END, FACE UP

ADA DIMENSIONS AND CLEARANCES DETAIL BA SCALE 3/8":1'

ADA DIMENSIONS AND CLEARANCES SECTION BC-BC SCALE 3/8" : 1' -

BY APPROVAL

ADA CLEARANCE ELEVATIONS ADDED PER PLAN REIVEW 2 PAGE 1; ARCHITECTURAL NOTE 1 OCCUPANCY NOTE ADDED - THIS PAGE PRELIMINARY COPY REVISION NOTES

PROJECT

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

** NOTE: PC TO PROVIDE AND INSTALL WATER LINE CONNECTIONS FROM FILTRATION SYSTEM TO EQUIPMENT.

8.1

18

AIR CURTAIN M/N: AA100 READY ACCESS

25

28 18

27

21

19 28

31

8

8"

W2

D1

26 31

OPTIONAL 36" AIR CURTAIN M/N: N236

26 W3

FIRE EXTINGUISHER

D2

OPTIONAL AIR CURTAIN M/N: AA100

33

READY ACCESS

26 31

16

ELEVATED ABOVE FLOOR

MOP SINK M/N: -

26

NSF Walk In Cooler 23

28

LAVATORY SINK M/N PF5404 ADA APPROVED

15

Intra

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

OPTIONAL AIR CURTAIN M/N: AA100

22

READY ACCESS

SOAP DISPENSER M/N: LTX-12 GOJO

25

28

23

13.1

31

CONDENSATE DRAIN TO ADJACENT FLOOR SINK

Water Closet

NOTE

E.C. TO VERIFY ELECTRICAL AND DATA CONNECTIONS FOR OWNER PROVIDED EQUIPMENT.

SOAP DISPENSER M/N: LTX-12 Paper Towel Dispenser - Wall Mount M/N: ASI0210

ROLL FROM THIS END, FACE UP

Paper Towel Dispenser Wall Mount M/N: ASI0210

13

(2X) SERVING TRAY - WALL MOUNT M/N: WS-12X36 TRUE

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING EQUIPMENT PLAN

13 PRELIMINARY USE ONLY

00r 10/12/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

GAS MAIN REMOVAL - THIS PAGE PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

2. WALK UP WINDOW LOCATION - IF BUILDING IS A DOUBLE SIDED DIVE THRU, REPLACE LEFT PANE OF FRONT WALL WINDOW WITH READY ACCESS 600 SERIES WINDOW FOR WALK UP CUSTOMERS. 3. DRIVE THRU WINDOW SPECS - USE READY ACCESS 600 SERIES WINDOW, BLACK FRAME. INCLUDE AIR CURTAINS ABOVE SERVICE WINDOWS WHEN REQUIRED BY LOCAL CODE 4. FRONT COUNTER HAND WASH SINK - INSTALL HAND WASH SINK ON THE SIDE OF THE BUILDING OPPOSING THE DRIVE THRU WINDOW (REFERENCE SITE PLAN)

ROLL FROM THIS END, FACE UP

1. HVAC SYSTEM - IN WARM WEATHER CLIMATES, REPLACE 3 TON HVAC CONDENSING UNIT WITH 5-6 TON UNIT or 5-6 TON SPLIT SYSTEM

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of 54

EQUIPMENT NOTES:

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING EQUIPMENT SCHEDULE

PRELIMINARY USE ONLY

14

00 03/04/21 REV DATE

EDK BY APPROVAL

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

HVAC Disconnect 60A VERIFY SIZE

32 HVAC Condensor VERIFY SIZE

ROLL FROM THIS END, FACE UP

Milbank

Daikin

11 33'-2 16 " (INSIDE SHEETROCK FACE FRONT WALL TO BACK OF BLOWER)

WALL TO FACE)

1'-11 15 16" (INSIDE OF PARAPET

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 1-12.SLDDRW, 00, 6/13/2022, 3 of

REVISION

00

32.1 HVAC Blower Unit M/N: VERIFY SIZE

2'-6 58" (INSIDE OF PARAPET WALL TO FACE)

Daikin (INSIDE BULDG)

SECTION AJ-AJ

AJ

3.2 CDF0600 A ICE MAKER CONDENSER MANITOWOC

AJ FRONT

REAR

1.1 Walk In Cooler - Evaporator M/N: LEL0095AS6AMAB0200

7

Larkin

1.3 Walk-In Cooler - Condensing Unit M/N: LHT-010-X6-BFM

Bathroom Fan Mfg

AIR KING Model: AK80LS6

80 CFM/0.5 Sones @ 0.10"SP. 57 CFM @ 0.25 SP.

Larkin

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING MECHANICAL PLAN

PRELIMINARY USE ONLY

00r - Mechanical Plans this page. (Plan Review: Page 2 Mechanical Note 1)

15

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

AIR CURTAIN

B-16

B-2,4

B-5,7

B-10

B-?,?

*4 *2

*2

CM

*3

20A

*3 *5

*3 20A

*3 30A

*3

*3

*1

*1

*3

ROLL FROM THIS END, FACE UP

B-14

*3

*3

A-?

A-25

30A

B-9,11 CM

HVAC CONNECT 10KVA A-13,15

A-29

*1

*1

B-18

*1 30A 30A

*1

GFCI

A-23 A-27

B-21,23 B-13,15

*1

WALK IN COOLER DISCONNECT

*1

B-10 A-17

B-20

OCCUPANCY SENSOR LB

AIR CURTAIN

B-22

AIR CURTAIN

*2

*2

B-24

*3

20A

*3

B-1,3

*3

30A

B-25,27

*3

*3

20A

B-?,?

*3

MP PANEL A GFCI

30A

1'-6"

B-6,8

B-26

ALL OUTLETS IN KITCHEN AREA THAT ARE ACCESSIBLE ARE GFCI PROTECTED PER ARTICLE: 210.8 (B) (2) AND (5). PER NEC 410.130 G, ALL FLOURESCENT LUMINARIES WITH DOUBLE ENDED LAMPS, THAT CAN BE SERVICED IN PLACE, SHALL HAVE AN INTERNAL OR EXTERNAL DISCONNECT. PER NEC 422.31, LOCK OUT DEVICE SHALL BE PROVIDED FOR HOT WATER TANK AT PANELBOARD OR DISCONNECT AT HOT WATER TANK. ALL OUTLETS AND SWITCHES NEED TO BE INSULATED WITH LOW E FOAM, IF THERE ARE GAPS, OTHERWISETHEY NEED TO BE GASKETED OR CAULKED ON INTERIOR OF BUILDING. ALL OUTLETS TO BE GFI AT PANEL OR GFI RUN EXCEPT FOR 220V. OCCUPANCY SENSOR IN RESTROOM PER C405.2.2.2 DAYLIGHT ZONE CONTROLS PER 2019 ASHRAE 90.1 9.4.1.1 (e) EXTERIOR LIGHTING CONTROL PHOTOCELL PER 2019 ASHRAE 90.1 9.4.1.4 AUTOMATIC TIME SWITCHES SHALL HAVE A MIN 7 DAY CLOCK & BE CAPABLE OF BEING SET FOR 7 DIFFERENT DAY TYPES PER WEEK AND INCORPORATE AN AUTOMATIC HOLIDAY "SHUT-OFF" FEATURE, WHICH TURNS OFF ALL LOADS FOR AT LEAST 24 HRS & THEN RESUMES NORMALLY SCHEDULED OPERATIONS. AUTOMATIC TIME SWITCHES SHALL ALSO HAVE PROGRAM BACK-UP CAPABILITIES, WHICH PREVENT THE LOSS OF PROGRAM & TIME SETTINGS FOR AT LEAST 10 HRS, IF POWER IS INTERRUPTED. THE OVERRIDE SWITCH SHALL PERMIT MANUAL OPERATION, AND WHEN INITIATED, SHALL PERMIT THE CONTROLLED LIGHTING TO REMAIN ON FOR A MAX OF 2 HOURS. WATER HEATER BREAKER HAS LOCKOUT FEATURE FOR SERVICING ARTICLE 422.31 (B) WALK-IN COOLER BREAKER HAS LOCKOUT FEATURE FOR SERVICING

• •

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - PLAN VIEW

PRELIMINARY USE ONLY

B-28

1'-0" 5'-2"

NOTES:

• • • • •

METER BASE

*5

CM = CEILING MOUNT

LB

• •

A-1,3 GFCI

*5

CM

• •

WATER HEATER

EXH. FAN

*3

*4

$

GFCI SP PANEL B

00r - Daylight Control / Exterior lighting notes. (Plan Review: Page 2 Energy Note 3&4)

$

ROLL FROM THIS END, FACE UP

30A

*1

B-30

B-17,19

$$

*1

2X2 LED 40W FIXTURE

GFCI = GROUND FAULT CIRCUIT INTERUPT MB = METER BOX

EXHAUST FAN

S/P= SERVICE PANEL

OCCUPANCY SENSOR

DUPLEX

EXIT SIGN (LESS THAN 5W)

DOUBLE DUPLEX

SWITCH

HARDWIRE

*1 = 18" to bottom of box AFF *2 = 30" to bottom of box AFF *3 = 40" to bottom of box AFF *4 = 84" to bottom of box AFF *5 = 90" to bottom of box AFF *6 = 96" to bottom of box AFF

220V OUTLET 3

$ 3-WAY SWITCH DUPLEX HALF HOT JUNCTION BOX

16

00s 10/21/21 EDK 00r EDK 10/12/21 00 03/04/21 EDK BY APPROVAL REV DATE

OUTLETS MOVED PER VISUAL INSPECTION, NEW LOCATIONS PER TOM @HB DAYLIGHT / EXTERIOR LIGHTING CONTROL NOTE ADDED - THIS PAGE PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

CONFIRM ELECTRICAL ACCOMMODATIONS FOR ICE MAKER CONDENSING UNIT.

A-19

FRONT

REAR

A-23 A-21

ROLL FROM THIS END, FACE UP

A-5,7

Line Set for remote Ice Condenser verify position

A-9,11

ROLL FROM THIS END, FACE UP

INTERNAL ID / DWG. FILE NAME / REV# / LAST PLOT DATE / SHEET OF SHEETS: HBC-O6S, Drive Thru Building-HB TB 13-28.SLDDRW, 00, 6/13/2021, 18 of 54

REVISION

00

PHOTO EYE DUPLEX JUNCTION BOX Drawing Scale:0.5:12 Plot Scale: 1:1 Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - ROOF PLAN VIEW

PRELIMINARY USE ONLY

17

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

UNDER AWNING FLOOD

HB

HB

ROLL FROM THIS END, FACE UP

HB

EXIT SIGN LB

LB

$$

(LESS THAN 5W)

3'-0"

LB

LB

LB

A-25

WALK IN COOLER DISCONNECT

A-23 UNDER AWNING FLOOD

FLOOD

$

$ A-17

(THIS IS AN OPTIONAL CIRCUIT, NOT ON ALL BUILDINGS)

LB

LB

LB

LB

EXH. FAN WALK IN COOLER LIGHT AND FAN

HB

UNDER AWNING FLOOD

HB

GFCI

HB

B-28

8'-0"

5'-0" 17'-0" 23'-0"

TIMER SWITCH $ SWITCH $

EXIT SIGN (LESS THAN 5W)

WALL PACK LED 30W

LB

JUNCTION BOX DUPLEX

2X2 LED 40W FIXTURE

LIGHTING

8" LED LIGHTING 30W HB = 96" FROM BOTTOM OF SIDING FLOOD = 127" FROM BOTTOM OF SIDING *1 = @84" AFF

NOTES

ALL FLOURESCENT LUMINARIES WITH DOUBLE ENDED LAMPS, THAT CAN BE SERVICED IN PLACE, HAVE AN INTERNAL OR EXTERNAL DISCONNECT.

•

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - PLAN VIEW

PRELIMINARY USE ONLY

18

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

11'-0"

ROLL FROM THIS END, FACE UP

REVISION

00

DOUBLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B16

SINGLE BOX

ETHERNET 1 PORT LOW VOLTAGE / N/A ETHERNET CAT-5,6,7 Circuit #: TV1 DOUBLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B22

SINGLE BOX

ETHERNET 1 PORT LOW VOLTAGE / N/A ETHERNET CAT-5,6,7 Circuit #: KDS

SINGLE BOX

ETHERNET 1 PORT LOW VOLTAGE / N/A ETHERNET CAT-5,6,7

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B20

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - FRONT ELEVATION

DOUBLE BOX 220V / 30A NEMA L6-30R Wires: 2+G NM 10-2 Circuit #: B13,15

PRELIMINARY USE ONLY

DOUBLE BOX 220V / 30A NEMA L6-30R Wires: 2+G NM 10-2 Circuit #: B21,23

19

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B18

DOUBLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B16

7 11'-9 16 "

11'-7 15 16"

9 9'-5 16 "

9 8'-1 16 "

7 5'-1 16 "

4'-11 15 16"

3'-7 15 16" 9 4'-1 16 "

1'-8 78"

LEADERS ATTACHED TO STUD SIDE

0" 9 81"

DOUBLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B22

ROLL FROM THIS END, FACE UP

1'-6"

3'-4"

8'-0"

SINGLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B22

SINGLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B22

DOUBLE BOX 220V / 30A NEMA L6-30R Wires: 2+G NM 10-2 Circuit #: B9,11

DOUBLE BOX 220V / 30A NEMA L6-30R Wires: 2+G NM 10-2 Circuit #: B17,19

00s EDK 10/21/21 00 03/04/21 EDK BY APPROVAL REV DATE

MOVED OUTLETS PER INSTRUCTIONS FROM TOM @ HB, REMOVED TWO UNDERCOUNTER OUTLETS PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

DOUBLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B14

SINGLE BOX

ETHERNET 1 PORT LOW VOLTAGE / N/A ETHERNET CAT-5,6,7 Circuit #: POS 4&5

SINGLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B14

ROLL FROM THIS END, FACE UP

SINGLE BOX

ETHERNET 1 PORT LOW VOLTAGE / N/A ETHERNET CAT-5,6,7 Circuit #: POS 4&5 For Access Point

LOW VOLTAGE / N/A Wires: N/A ETHERNET CAT-5,6,7 Circuit #: POS HOMERUN

SINGLE DUPLEX 120V / 20A NEMA 5-15R Wires: 2+G 12-2 NM Circuit #: B10

UPS

TOAST MERAKI ROUTER

Internet

SWITH FOR MERAKI ROUTER ITEMS

AUXILIARY ROUTER

Internet

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B14

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B14

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - RIGHT ELEVATION

DOUBLE BOX 220V / 20A NEMA L6-20R Wires: 2+G NM 12-2 Circuit #: B5,7

PRELIMINARY USE ONLY

DOUBLE BOX 220V / 20A NEMA L6-20R Wires: 2+G NM 12-2 Circuit #: B2,4

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B10

20

DOUBLE BOX 220V / 30A NEMA L14-30R Wires: 3+G NM 10-3 Circuit #: B?,?

36'-10 34"

28'-9 41"

24'-9 41"

16'-10 34"

11'-5 41"

14'-1 41" DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B14

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B10

SINGLE GANG GFCI 110V / 20A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B10

00s EDK 10/21/21 00 03/04/21 EDK BY APPROVAL REV DATE

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B10

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B10

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B10

MOVED OUTLETS PER INSTRUCTIONS FROM TOM @ HB PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

1'-6"

3'-4"

SINGLE BOX

ETHERNET 2 PORT LOW VOLTAGE / N/A NONE Wires: N/A ETHERNET CAT-5,6,7 Circuit #: POS 6

7 9'-2 16 "

0"

7'-10 78"

13'

6'-1 41"

LEADERS ATTACHED TO STUD SIDE

1'-6"

3'-4" 2'-6"

5'-0"

8'-2"

SWITH FOR AUXILIARY ROUTER

ROLL FROM THIS END, FACE UP

REVISION

00

SINGLE BOX 120 / 240 / VARIES NEMA#: HARDWIRE FLEX CONNECTOR Wires: N/A Wire Type: NM Wire Sizing: SIZED PER AMPERAGE Circuit #: A1,3

STREET AND BUILDING SIGNS

7'-6"

PARKING LOT AND EXTERIOR BUILDING LIGHTING

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - REAR ELEVATION

PRELIMINARY USE ONLY

21

0"

6'-4 58"

2'-5 38"

3'-8"

STATIC MENU BOARD AT ORDER STATION

ALARM POWER DOOR SWING DETERMINES POSITION ROLL FROM THIS END, FACE UP

TIIME CLOCKS

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

SINGLE BOX

ETHERNET 2 PORT LOW VOLTAGE / N/A NONE Wires: N/A ETHERNET CAT-5,6,7 Circuit #: POS 1&2

ROLL FROM THIS END, FACE UP

REVISION

00

(2X) 2" CONDUIT

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - LEFT ELEVATION

DOUBLE BOX 220V / 30A NEMA 6-30R Wires: 2+G NM 10-2 Circuit #: NOT ASSIGNED

PRELIMINARY USE ONLY

SINGLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B26

22

DOUBLE BOX 220V / 30A NEMA L14-30R Wires: 3+G NM 10-3 Circuit #: B25,27

00s 10/21/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

DOUBLE BOX 220V / 30A NEMA L14-30R Wires: 3+G NM 10-3 Circuit #: B1,3

0"

6'-1 21"

7'-6 34" 7'-5 21"

5 10'-4 16 "

11'-6 34"

12'-10 34"

15'-5 41"

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B26

ROLL FROM THIS END, FACE UP

DOUBLE BOX 220V / 30A NEMA 6-30R Wires: 2+G NM 10-2 Circuit #: B6,8

15'-6 34"

2'-6" 3'-4" SINGLE GANG GFCI 110V / 20A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B28

18'-2 34"

11 20'-10 16 "

5 42'-8 16 "

3'-4"

5'-10"

8'-0"

LOW VOLTAGE PIPE CHASE FROM CEILING CAVITY TO FLOOR CAVITY FOR LOW VOLTAGE COMS.

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G NM 12-2 Circuit #: B24

DOUBLE DUPLEX 120V / 20A NEMA 5-20R Wires: 2+G 12-2 NM Circuit #: B24 SINGLE BOX - ETHERNET 4 PORT LOW VOLTAGE / N/A NONE Wires: N/A ETHERNET CAT-5,6,7 Circuit #: POS 3

MOVED OUTLETS PER INSTRUCTIONS FROM TOM @ HB PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

SECTION IN BATHROOM LOOKING TOWARD FRONT OF BUILDING

ROLL FROM THIS END, FACE UP

SECTION IN BATHROOM LOOKING TOWARD HALLWAY

HARDWIRE CONNECTION WATER HEATER (SEE PG.22)

6'-2"

7'-6"

SINGLE DUPLEX 120V / 15A NEMA 5-15R Wires: 2+G NM 14-2 Circuit #: B10

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - AUXILIARY ELEVATIONS

0"

2'-7 34"

8 41"

SECTION IN HALLWAY LOOKING TOWARD BATHROOM

SECTION IN BATHROOM LOOKING TOWARD BACK OF BUILDING

PRELIMINARY USE ONLY

23

00s 10/21/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

MOVED OUTLETS PER INSTRUCTIONS FROM TOM @ HB PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

MAIN LOAD CENTER

SECOND LOAD CENTER

MAIN BREAKER

YES -200Amp -1 PHASE, 3 WIRE, 120/240V VOLTAGE: 240/120 1 Phase -MAIN BREAKER: 200A, 22K AIC MAIN BREAKER FACTORY INSTALLED AMPERAGE: 200 SPACES: 30 MAIN LUG ONLY: NO MAIN LUG: 100K AIC MAX. RATED (SEE WIRING DIAGRAM FOR DETAILS) PHASE:1 MOUNTING: FLUSH NEMA 3R -CONVERTIBLE MAIN LUG/MAIN BREAKER -TYPE 3R OUTDOOR ENCLOSURE CKT CKT -ANSI 61 GRAY POWDER COATED ENCLOSURE LOA LOA GFCI BREAKERGFCI BREAKER -DESIGNED FOR USE WITH PLUG-ON NEUTRAL BREAKERS # # DESC. SIZE BREAKER VOLTAGE WIRE D SIZE VA PHASE D VA WIRE SIZE VOLTAGE DESC. BREAKERSIZE 40 NO 240 8/2 3000 A 0SPACE 1 WATER HEATER 2 *INDICATES POSITIONING NUMBERS TO HELP WITH THE MANUAL 3 WATER HEATER 40 NO 240 8/2 3000 B 0SPACE 4 PLACEMENT OF BREAKERS ON THE MECHANICAL VIEW 5 HVAC -Outside 30 NO 240 10/2 4200 A 0SPACE 6 RISER DIAGRAM 7 HVAC -Outside 30 NO 240 10/2 4200 B 0SPACE 8 M/N: PN3048B1200C 9 Cooler - Outside 20 NO 240 12/2 780 A 0SPACE 10 11 Cooler - Outside 20 NO 240 12/2 780 B 0SPACE 12 13 HVAC COND-Inside 15 NO 240 14/2 250 A 0SPACE 14 15 HVAC COND-Inside 15 NO 240 14/2 250 B 0SPACE 16 MAIN 17 Cooler -Inside 20 NO 120 12/2 0 A 0SPACE 18 M/N: 78205162220 / 324C 400AMP - 120/240V 19 Roof Recept. 20 NO 120 12/2 0 B 0SPACE 20 SINGLE PHASE SURFACE MOUNT 21 Signs 20 NO 120 12/2 0 A 0SPACE 22 UG ACCESS BYPASS: MCC 23 Lights -Outside 20 NO 120 12/2 0 B 0SPACE 24 NEMA 3R 4 JAW 25 Lights - Inside 15 NO 120 12/2 0 A 0SPACE 26 LINE: STUDS / LOAD: #4 27 Air Curtain -L 20 NO 120 12/2 0 B 0SPACE 28 600MCM / NEUTRAL: STUDS 29 Air Curtain -R 20 NO 120 12/2 0 A 0SPACE 30 (6" DEEP) 15180 (15.31KVA) TOTAL AMPS = TOTAL VA = 69.63 PHASE A 8230 PHASE B 8230 (VA): (VA): 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43

-1 PHASE, 3 WIRE, 120/240V -MAIN BREAKER: 200A, 22K AIC MAIN BREAKER FACTORY INSTALLED MAIN LUG: 100K AIC MAX. RATED (SEE WIRING DIAGRAM FOR DETAILS) -CONVERTIBLE MAIN LUG/MAIN BREAKER -TYPE 3R OUTDOOR ENCLOSURE -ANSI 61 GRAY POWDER COATED ENCLOSURE -DESIGNED FOR USE WITH PLUG-ON NEUTRAL BREAKERS

ROLL FROM THIS END, FACE UP

PANEL SCHEDULE A AIC

10,000

M/N: PNW3048B1200C

MAIN

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44

PANEL SCHEDULE B AIC

10,000

Drawing Scale

Plot Scale: Internal ID:

HBC-O6S

1:12 1:1

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - PANEL SCH & RISER DIAG

PRELIMINARY USE ONLY

24

ONELINE DIAGRAM 3" STUBBED FOR POWER CO.

(2 1/2") WITH (3) 250 MCM XHHW AL (1) #2 XHHW AL PANEL A 200A MLO 320A / 240V / 1P / 3W METERBASE

240V / 1P / 3W 200 200/3

200 200/3

PANEL B 200A MLO

320

(3") TO UTILITY; TO BE CONNECTED AFTER BUILDING PLACEMENT BY OTHERS

00r 10/12/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

#4 BARE COPPER COILED TO BE CONNECTED AFTER BUILDING PLACEMENT BY OTHERS

240V / 1P / 3W

CONNECTION TO BUILDING STEEL (1) 1/0 XHHW AL

MOVED ONE SUB-PANEL TO LEFT SIDE OF METER BASE AND SHIFTED ENTIRE SET TOWARD DOOR PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

MAIN BREAKER

Yes -200Amp VOLTAGE: 240/120 1 Phase SPACES: 30 AMPERAGE: 200 MAIN LUG ONLY: YES MOUNTING: FLUSH NEMA 3R (2) 2 1/2" w/ (3) 250 MCM XHHT AL PHASE:1 CKT (1) #2 XHHW AL LOA LOA GFCI BREAKERGFCI BREAKER # CKT # DESC. SIZE BREAKER VOLTAGE WIRE D SIZE VA PHASE D VA WIRE SIZE VOLTAGE DESC. BREAKERSIZE 1 Recept 30 Recept 30 NO 240 10/2 10/3 240 No A 2 3 Recept 30 Recept 30 NO 240 10/2 10/3 240 No B 4 5 Recept 30 Recept 30 NO 240 10/2 10/2 240 No 6 A 7 Recept 30 Recept 30 NO 240 10/2 10/2 240 No 8 B 9 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO 10 A 11 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO B 12 13 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO A 14 15 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO 16 B 17 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO 18 A 19 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO 20 B 21 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO A 22 23 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO B 24 25 Recept 20 Recept 30 NO 240 10/2 12/2 120 NO 26 A 27 Recept 30 NO 240 10/2 12/2 120 NO 20 Bathroom 28 B 29 Recept 20 NO 240 10/2 12/2 120 NO 20 1/2 Hots 30 A 0 (0KVA) TOTAL AMPS = TOTAL VA = 0A PHASE A: 0 VA PHASE B: 0 VA

REVISION

00

POS1 PRINTER 2 FUTURE LABEL 2 SPARE 2 LOCATION @ 26" O.F.F.

LOCATION @ 96" O.F.F. LOCATION @ 60" O.F.F.

ROLL FROM THIS END, FACE UP

KDS 3 FUTURE LABEL 3 LOCATION @ 60" O.F.F.

CAT-6e HOME-RUN LOCATION @ 96" O.F.F.

TV 2

KDS 2 KDS 2

ACCESS POINT TOUT

(ON ROOF)

LOCATION @ 96" O.F.F.

KDS 1 KDS 1

TUC TV 1

T

VHR SHR

+-

POS1 PRINTER 1

FUTURE KDS FUTURE LABEL LOCATION @ 60" O.F.F.

ROLL FROM THIS END, FACE UP

LOCATION @ 60" O.F.F.

FUTURE LABEL 1 SPARE 1 LOCATION @ 26" O.F.F.

NOTES:

CAT-5e

THERMOSTAT IS A 7 DAY PROGRAMABLE UNIT AND DOES NOT ALLOW SIMULSTANEOUS HEATING AND COOLING TO BE ACTIVE. UNDER COUNTER ITEMS - TUC, POS2 ITEMS THAT ARE MOUNTED AT 6 TO 12 INCHES OFF OF CEILING - POS1, T, VHR, SHR TOUT - IS AT OR NEAR TOF ELEVATION T = TELEPHONE VHR = VIDEO HOME RUN SHR = SPEAKER HOME RUN POS = POINT OF SALE

• • • • • • • •

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ELECTRICAL PLAN - LOW VOLTAGE

PRELIMINARY USE ONLY

PHONE SECURITY CAMERA INTERNET SERVICE ON ROOF TOWER

25

00 03/04/21 REV DATE

EDK BY APPROVAL

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

ROLL FROM THIS END, FACE UP

HEAT TRAP

3/4"

3/4"

WATER HEATER OVERFLOW DRAIN LINE (TO MOP SINK)

HOSE BIB 1/2"

1/2" 1/2"

1/2"

1/2"

N

1" ITY C O T

CO

3/4"

1/2"

1/2"

CTIO E N N

3/4" 1/2" 1/2"

FIRST 8' OF PIPING TO BE INSULATED WITH 1/2" INSULATION

3/4"

1/2"

1/2"

ROLL FROM THIS END, FACE UP

3/4" 3/4" 1/2"

3/4" 1/2"

3/4"

1/2"

3/4"

1/2"

3/4" THESE (2) ANGLE STOPS MUST BE LOCATED BEHIND HANDWASH SINK, THE HANDWASH SINK CAN ALTERNATIVELY BE ON EITHER SIDE OF FRONT COUNTER DEPENDENT ON SITE LAYOUT

00r - Water Plans this page. (Plan Review: Page 3 Plumbing Note 1)

NOTES

WATER LINES ARE TO BE OF AN APPROVED MATERIAL SUCH AS COPPER, PEX, OR OTHER APPROVED MATERIALS.

•

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PLUMBING PLAN - WATER

PRELIMINARY USE ONLY

26

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

UPS

TOAST MERAKI ROUTER

Internet

SWITH FOR MERAKI ROUTER ITEMS

AUXILIARY ROUTER

Internet

ROLL FROM THIS END, FACE UP

SWITH FOR AUXILIARY ROUTER

C C

H

C

ANGLE STOP

ANGLE STOP

SINK SUPPLY

SECTION AS-AS

C

ANGLE STOP

ROLL FROM THIS END, FACE UP

SECTION AT-AT

WATER HEATER SUPPLY

HC

OPTIONAL ESPRESSO MACHINE (GETS ITS OWN DRAIN LINE LIKE THE OTHER 3) DRAIN LINE ROUTED TO FLOOR SINK ON THE LEFT

ANGLE STOP

HCC

C

SECTION AX-AX

WATER FILTER M/N: RG-WTR-SYS

Plot Scale

Internal ID:

HBC-O6S

H

C

RANCILIO

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PLUMBING PLAN - WATER ELEVATION

SECTION AV-AV

ANGLE STOP ESPRESSO DRAIN LINES

ANGLE STOP LOCATIONS ARE APPROXIMATE

0.3125:12 1:1

CC

HC

RANCILIO

ANGLE STOP

ANGLE STOP

Drawing Scale:

CC

WATER FILTER M/N: RG-WTR-SYS

ESPRESSO DRAIN LINES

ANGLE STOP

SECTION AU-AU PRELIMINARY USE ONLY

27

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

VTR VTR VTR

VTR ROLL FROM THIS END, FACE UP

1-1/2" 1-1/2" 1-1/2"

VTR

1-1/2"

2"

VENT 3" 1-1/2"

1-1/2"

E

S

A RE

CLEANOUT

CLEANOUT

IN EL

-G N NO

3"

E

S

OPTIONAL DIRECT DRAIN TO BE PLACED IN VENT LINE FOR LOCATIONS THAT REQUIRE A DIRECT CONNECTION. CAP IF UNUSED.

A RE

G

1-1/2" CLEANOUT

THIS FLOOR SINK SERVICES THE TRIPLE SINK AND THE STAND UP ICE MACHINE CONDENSATE DRAIN

IN EL

3" OUTSIDE OF BUILDING BY OTHERS

3" 2"

VTR

ROLL FROM THIS END, FACE UP

THIS FLOOR SINK SERVICES THE WALK IN COOLER CONDENSATE DRAIN TRAP PRIMER

2" THIS FLOOR SINK SERVICES (2) ESPRESSO MACHINES CLEANOUT 3"

TRAP PRIMER THIS FLOOR SINK SERVICES AN ESPRESSO MACHINE

1-1/2"

CLEANOUT

2"

1-1/2"

TRAP PRIMER CLEANOUT

2"

2"

00u - DWV Plan update this page. (Plan Review: Page 2&3 Plumbing Notes 1,2,3&4)

NOTES

• •

DWV TO BE EITHER ABS OR DWV APPROVED PVC. THESE PLUMBING PLANS ARE PRESCRIPTIVE AND DIAGRAMATIC IN NATURE AND ARE IN NO WAY INTENDED TO BE THE ACTUAL PATH OR AN EXACT INSTALLATION THAT THE PLUMBER SHALL FOLLOW. THE PLUMBER IS A PROFESSIONAL AND MAY ENCOUNTER SITUATIONS WHERE THE PLUMBING MAY / WILL BE DIFFERENT THAN PICTURED ABOVE.

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PLUMBING PLAN - DWV

PRELIMINARY USE ONLY

VTR = VENT THRU ROOF

00r - DWV Plan this page. (Plan Review: Page 3 Plumbing Notes 2,3&4)

28

00u 12/03/21 EDK 00r EDK 10/13/21 00 03/04/21 EDK BY APPROVAL REV DATE

DWV

UPDATED PLAN PER PLUMBING CONTRACTOR INPUT AND PLAN REVIEW: PAGE 2&3, PLUMBING NOTES 1,2,3 & 4 ISOMETRIC DWV PLAN PER PLAN REVIEW: PAGE 3, PLUMBING NOTE 2,3 & 4 PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

ROLL FROM THIS END, FACE UP

(FRONT OF STEEL) 0"

12'-8"

T 2X4 SUPPORT BLOCKING EVERY 3' 2" PVC ROOF DRAINS

T

15'-2 21"

NOTE

SOME DRAINS ARE OBSCURED BY PARAPET, BUT ARE AT DIMENSIONED LOCATION AND CENTERED ON BUILDING CENTERLINE

ROLL FROM THIS END, FACE UP

28'-8"

31'-2 21"

NOTES:

SECTION T-T

DWV TO BE EITHER ABS OR DWV APPROVED PVC. THESE PLUMBING PLANS ARE PRESCRIPTIVE AND DIAGRAMATIC IN NATURE AND ARE IN NO WAY INTENDED TO BE THE ACTUAL PATH OR AN EXACT INSTALLATION THAT THE PLUMBER SHALL FOLLOW. THE PLUMBER IS A PROFESSIONAL AND MAY ENCOUNTER SITUATIONS WHERE THE PLUMBING MAY / WILL BE DIFFERENT THAN PICTURED ABOVE. ROOF DRAIN LOCATIONS ARE APPROXIMATE, ACTUAL LOCATION TO BE DETERMINED BY PLUMBING CONTRACTOR 00r - Roof Drain Plan this page.

• •

•

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PLUMBING PLAN - ROOF DRAINS

SCALE 1 : 64 PLAN VIEW ROOF DRAIN LOCATIONS (CENTERED ON CL OF BUILDING)

3 ( 16 " : 1')

(Plan Review: Page 3 Plumbing Note 2)

PRELIMINARY USE ONLY

29

00r 10/13/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

ROOF DRAIN PLAN PER PLAN REVIEW: PAGE 3, PLUMBING NOTE 2 PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

25'-1121" AWNING TO AWNING OUTSIDE DIM.

NOTE

The sloped roof elevation shown here is nonstandard. Refer to elevation pages 31,33,35 and 37 for standard roof design.

14'-4" OVER COLUMNS

ROLL FROM THIS END, FACE UP

10'-421" CENTER TO CENTER STANCHON TUBES

6'-11 15 16"

11 7'-9 16 "

STUCCO COLUMNS

ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE)

AWNINGS

4'-3 81"

STACKED STONE FACIA

ROLL FROM THIS END, FACE UP

STONE LEDGE

1 12'- 16 " AWNING HEIGHT FROM BOTTOM OF STEEL

9'-6"

5'-6"

STUCCO

11'-3 78" ROOF TO PARAPET CONNECTION

1'-4"

5'-9 34" COLUMN TO AWNING OVERHANG

2'-0"

1'-0"

TOP OF STEEL

7'-10" 10'-7 21" BETWEEN EFIS COLUMNS

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRONT ELEVATION

PRELIMINARY USE ONLY

30

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

25'-1121" AWNING TO AWNING OUTSIDE DIM. 15'-721" OVER PARAPET DETAIL

ROLL FROM THIS END, FACE UP

10'-421" CENTER TO CENTER STANCHON TUBES

14'-4" OVER COLUMNS

6'-11 13 16"

1 8'- 16 "

STUCCO COLUMNS

ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE)

AWNINGS

4'-381"

STACKED STONE FACIA

ROLL FROM THIS END, FACE UP

STONE LEDGE

1 12'-16 " AWNING HEIGHT FROM BOTTOM OF STEEL

9'-6"

5'-6"

STUCCO

11'-378" ROOF TO PARAPET CONNECTION

1'-4"

19'-378"

5'-934" COLUMN TO AWNING OVERHANG

2'-0"

1'-0"

TOP OF STEEL

7'-10" 10'-7 21" BETWEEN EFIS COLUMNS

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRONT ELEVATION

PRELIMINARY USE ONLY

31

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

NOTE

The sloped roof elevation shown here is nonstandard. Refer to elevation pages 31,33,35 and 37 for standard roof design.

ROLL FROM THIS END, FACE UP

EFIS / STUCCO ARCHITECTURAL DETAIL

STUCCO

STUCCO COLUMNS

ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE)

AWNINGS

KEY LOCK BOX

11'-378"

3'-4"

STACKED STONE FACIA

ROLL FROM THIS END, FACE UP

6'-0"

STONE LEDGE

6'-1021" R.O.

2'-8 78"

2'-11 78"

SERVICE OUTLET

1'-4"

1'-181"

TOP OF STEEL

5 2'-116 "

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING REAR ELEVATION

PRELIMINARY USE ONLY

1'-238" 3"

1'-238"

2'-0"

3"

4'-1034" 7'-481"

3'-421"

32

3'-2 15 16"

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

STUCCO ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE) STUCCO COLUMNS

ROLL FROM THIS END, FACE UP

EFIS / STUCCO ARCHITECTURAL DETAIL

AWNINGS

KEY LOCK BOX

11'-378"

3'-4"

STACKED STONE FACIA

ROLL FROM THIS END, FACE UP

6'-0"

STONE LEDGE

6'-1021" R.O.

2'-8 78"

2'-11 78"

SERVICE OUTLET

1'-4"

1'-181"

TOP OF STEEL

5 2'-116 "

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING REAR ELEVATION

PRELIMINARY USE ONLY

1'-238" 3"

1'-238"

2'-0" 4'-1034" 7'-481"

33

3" 3'-421"

3'-2 15 16"

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

3 21'-4 16 "

11'-9 15 16"

SLOPE= 1:12 16 "

NOTE

The sloped roof elevation shown here is nonstandard. Refer to elevation pages 31,33,35 and 37 for standard roof design.

ROLL FROM THIS END, FACE UP

11'-9 15 16"

ROLL FROM THIS END, FACE UP

5'-0"

8'-0"

SLOPE= 2:12

TOP OF STEEL

3 21'-4 16 "

11'-9 15 16"

Drawing Scale

Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING RIGHT SIDE ELEVATION

PRELIMINARY USE ONLY

11'-9 15 16"

34

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

STANDING SEAM STEEL ROOF PANEL

2'-11 21" TOP OF SERVING TRAY

ROLL FROM THIS END, FACE UP

4'-3 81"

1 12'- 16 "

5'-6"

ADDRESS LETTERING IS 6" HIGH, 1" STROKE

ROLL FROM THIS END, FACE UP

ENAMEL COATED STEEL TRIM (SIDES AND SOFFIT) EFIS FOAM DETAIL COVERED BY STUCCO TOPCOATING

TOP OF STEEL

SERVING TRAY 3'-0" SERVING TRAY WIDTH 7'-10" R.O. 1'-10 41"

7 8'-1 16 " BETWEEN EFIS COLUMNS

3 21'-4 16 "

1'-10 41"

1'-10 41"

7 8'-1 16 "

1'-10 41"

NOTE

The sloped roof elevation shown here is nonstandard. Refer to elevation pages 31,33,35 and 37 for standard roof design. WALK UP COUNTER HEIGHT SHALL BE NO HIGHER THAN 34" ABOVE FINISH FLOOR Drawing Scale: 0.3125:12 THE HUMAN BEAN Plot Scale: Internal ID:

HBC-O6S

1:1

13'6" X 45' PREFABRICATED BUILDING LEFT SIDE ELEVATION

PRELIMINARY USE ONLY

36

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

6'-11 13 16"

ROLL FROM THIS END, FACE UP

EFIS FOAM DETAIL COVERED BY STUCCO TOPCOATING

16'-3 78"

2'-11 21" TOP OF SERVING TRAY

ROLL FROM THIS END, FACE UP

4'-3 81"

1 12'- 16 "

5'-6"

19'-3 78"

ADDRESS LETTERING IS 6" HIGH, 1" STROKE

TOP OF STEEL

SERVING TRAY 3'-0" SERVING TRAY WIDTH 7'-10" R.O. 1'-10 41"

7 8'-1 16 " BETWEEN EFIS COLUMNS

3 21'-4 16 "

1'-10 41"

1'-10 41"

7 8'-1 16 "

1'-10 41"

WALK UP COUNTER HEIGHT SHALL BE NO HIGHER THAN 34" ABOVE FINISH FLOOR Drawing Scale: Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING LEFT SIDE ELEVATION

PRELIMINARY USE ONLY

37

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

14'-4" OVER COLUMNS

Walk in Cooler Condenser

ROLL FROM THIS END, FACE UP

Remote Ice Condenser HVAC DISCONNECT

ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE)

AWNINGS

7" 2'-7 15 16"

1 81"

3'-2 58"

ROLL FROM THIS END, FACE UP

9 21"

7 41"

2"

DETAIL F SCALE 1 : 12

9 1 16 "

2'-10 21"

2'-11 38"

1 3'-2 16 "

F

2"

OVERLAP

7 8" SHEATHING

1'-0"

1'-0"

G

TOP OF FLOOR

I

DETAIL I SCALE 1 : 12 2"

3"

2'-6"

1 2'-3 16 "

5'-0" 1"

8'- 58"

DETAIL G SCALE 1 : 12

2 58" 1 2'-3 16 "

CABINET LAYOUT FOR REFERENCE ONLY, CABINET CONSTRUCTION TO BE VERIFIED BY CUSTOMER AND BUILDER BEFORE CONSTRUCTION COMMENCES. Drawing Scale: Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING FRONT INTERIOR ELEVATION

PRELIMINARY USE ONLY

38

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

ONSITE CONNECTION LINE (PARAPETS ARE CONNECTED TO BUILDING ONSITE)

ROLL FROM THIS END, FACE UP

1 3'-2 16 "

6 34"

9 15 16"

9 15 16"

AWNINGS

TOP OF FLOOR

6'-2 21" 1 3'-1 16 "

6'-4 58"

1 3'-1 16 "

CABINET LAYOUT FOR REFERENCE ONLY, CABINET CONSTRUCTION TO BE VERIFIED BY CUSTOMER AND BUILDER BEFORE CONSTRUCTION COMMENCES. Drawing Scale: Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING REAR INTERIOR ELEVATION

PRELIMINARY USE ONLY

39

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

3 21'-4 16 " COLUMN TO COLUMN

5'-0"

8'-0"

1'-6"

1'-6"

14'-2 21"

4'-0"

1'-0"

1'-0"

4'-0"

ROLL FROM THIS END, FACE UP

REVISION

00

UPS

TOAST MERAKI ROUTER

Internet

SWITH FOR MERAKI ROUTER ITEMS

AUXILIARY ROUTER

Internet

SWITH FOR AUXILIARY ROUTER

1'- 21"

ROLL FROM THIS END, FACE UP

1 3'-2 16 "

2'-7 15 16"

1 2"

TOP OF FLOOR

9'-8 34"

4'-6 81"

1'-10" 1 3'-2 16 "

3'- 81"

9'-10 78"

4'-6 81"

2'-7"

3X 4'-0" 3 8'- 16 "

CABINET LAYOUT FOR REFERENCE ONLY, CABINET CONSTRUCTION TO BE VERIFIED BY CUSTOMER AND BUILDER BEFORE CONSTRUCTION COMMENCES. Drawing Scale: Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING RIGHT SIDE INTERIOR ELEVATION

PRELIMINARY USE ONLY

40

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

1 3'-2 16 "

2'-7 15 16"

1'-0"

1'- 21"

3'-8" SOAP DISP.

1'-0"

3 8"

ROLL FROM THIS END, FACE UP

3'-2 58"

1'-0"

3'-2 58"

1'-0"

1 7'-6 16 "

4'-6" PAPER TOWEL DISP.

ROLL FROM THIS END, FACE UP

REVISION

00

TOP OF FLOOR

16'-8 81"

3'- 81"

1 3'-2 16 "

CABINET LAYOUT FOR REFERENCE ONLY, CABINET CONSTRUCTION TO BE VERIFIED BY CUSTOMER AND BUILDER BEFORE CONSTRUCTION COMMENCES. Drawing Scale: Plot Scale:

0.3125:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING LEFT SIDE INTERIOR ELEVATION

PRELIMINARY USE ONLY

41

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

PARAPET STRUCTURE

COMBINATION OF WOOD, STUCCO AND/OR METAL PANELING

ROLL FROM THIS END, FACE UP

2X BLOCKING AND BCI WEB STIFFENERS REQUIRED BY ENGINEERING, SEE BCI ROOF PLAN FOR DETAILS AS WELL AS ENGINEERING PRINTS 2X4 LAYING FLAT, ROOF CURB FOR PARAPET WALLS

00r - occupancy note added. (Plan Review: Page 2 Energy Note 2)

DUROLAST ROOFING MEMBRANE

5/8" ROOF PLYWOOD STEEL AWNING

VERSALAM BEAM

SUSPENDED DROP CEILING

9 1/2" ROSEBURG 400 RFPI

APPROVED HYDROTEX RAIN-GUARD WEATHER BARRIER SYSTEM

1.4E RIDGERIM LVL, RIM JOIST

ROCK VENEER LEDGER

DOUBLE TOP PLATES

ROCK VENEER

4 MIL VISQUEEN AGAINST INTERIOR SIDE OF ROOF BCIs

1/2 OSB R7.6 EIFS

R MAX R21 BATT OR EQUIVALENT BETWEEN STUDS

ROLL FROM THIS END, FACE UP

FRONT OF BUILDING

FRAMING SHEETROCK ALTRO® FLOORING BOTTOM PLATE 1

1 8" T&G SUBFLOOR 9 1/2" ROSEBURG 400 RFPI

STEEL C-CHANNEL

2X8 RIM JOIST 6 MIL VISQUEEN AGAINST FLOOR JOIST FOUNDATION

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING BUILDING SECTION 1

SUPPORT TUBE

PRELIMINARY USE ONLY

42

00r EDK 10/12/21 00 03/04/21 EDK BY APPROVAL REV DATE

UPDATED NOTE TO INCLUDE "HYDROTEX" PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

FRP CAULKING SHEETROCK KING STUD ROLL FROM THIS END, FACE UP

TRIMMER STUD EXPANDED FOAM INSULATION STORE FRONT WINDOW (BY OTHERS) BACKER ROD COLOR MATCHED CAULKING SILL STUD SHEETROCK

EXTERIOR DOOR JAMB

EXTERIOR RATED COLOR MATCHED CAULKING SUBSIDING APPROVED HYDROTEX RAIN-GUARD WEATHER BARRIER SYSTEM SUBSIDING

STUCCO BROWN COAT STUCCO COLOR COAT

APPROVED HYDROTEX RAIN-GUARD WEATHER BARRIER SYSTEM MORTAR STONE FACADE / STUCCO

TYPICAL WINDOW ENVELOPE DETAIL SCALE 1 : 2

EXTERIOR COLOR MATCHED CAULKING

PARAPET SUBSIDING

PVC COATED METAL FLASHING, DUROLAST MEMBRANE HEAT WELDED TO FLASHING ROOF CURB STUDS

TYPICAL DOOR ENVELOPE DETAIL SCALE 1 : 2

EFIS STUCCO BROWN COAT STUCCO COLOR COAT

ROLL FROM THIS END, FACE UP

DUROLAST PVC MEMBRANE ROOFING ROOFING FOAM, SLOPED FOR DRAINAGE ROOF SHEATHING

SUBSIDING

TYPICAL ROOF TO WALL ENVELOPE DETAIL SCALE 1 : 4 Drawing Scale: Plot Scale: Internal ID:

HBC-O6S

1:12 1:1

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING ENERGY ENVELOPE DETAL VIEWS

PRELIMINARY USE ONLY

43

00u 12/03/21 EDK 00 03/04/21 EDK BY APPROVAL REV DATE

ENERGY ENVELOPE DETAILS ADDED PER PLAN REIVEW 2: PAGE 2; ENERGY NOTE 2 PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

2'-0" 1'-6" 3'-6"

1'-0" 6"

3'-0"

2'-10"

3'-4"

ROLL FROM THIS END, FACE UP

5'-2 78"

5'-2 78" 1'-8 15 16"

2'-10"

3'-4"

2'-3"

3'-8" SOAP 3'-8" PAPER 2'-9" 9"

1'-6"

3'-0"

3'-4"

ADA CLEAR SPACE AT SINK

1'-6" 8"

6"

8" 1'-5"

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

SECTION A-A

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING BATHROOM ELEVATIONS

SECTION B-B

PRELIMINARY USE ONLY

44

SECTION C-C

00 03/04/21 EDK BY APPROVAL REV DATE

SECTION D-D

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

ROLL FROM THIS END, FACE UP

7 5'- 16 "

3" PVC RISER FOR A/C LINES

SECTION AI-AI SCALE 1 : 20

ROOF FOAM (SLOPING FOR DRAINAGE) 3" PVC RISER FOR ICE MACHINE

3 21"

SLOPE 1/2" : 1'

AI

11 8'-11 16 "

AI

4'-0"

1'-6"

(4X) ROOF DRAINS

2'-0"

2'-3 21"

2'-3 15 16"

3" PVC RISER FOR A/C LINES

10'-8 21"

5'-9 21"

2'-3 21"

3 21"

11 33'-2 16 "

DUROLAST ROOFING MEMBRANE

SLOPE 1/2" : 1'

5'-7"

SLOPE 1/2" : 1'

ROLL FROM THIS END, FACE UP

SLOPE 1/2" : 1'

3" PVC RISER FOR A/C LINES

2'-3 15 16"

2'-6" 2'-6 21"

13'-5 21"

4'-9 21"

2'-6 21"

3 13'- 16 "

3 39'-5 16 "

WIFI ROUTER CONDUIT

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING SLEEPER DETAILS

PRELIMINARY USE ONLY

45

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

4'-9 34" TO EXTERIOR

4'-0"

BUILDING SHEATHING

PAINTED PLYWOOD DOOR

5'-0"

SHORT PARAPET WALL

ROLL FROM THIS END, FACE UP

EXTENSION LADDER (ROOF ACCESS)

GROUND PLANE

SECTION H-H

Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PARAPET OPENING AND ROOF ACCESS

PRELIMINARY USE ONLY

46

00 03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

ROLL FROM THIS END, FACE UP

10'- 41"

4 X 8 PRESSURE TREATED BEAM FOR STANCHION TUBE MOUNTING (REQD. ON SIDES THAT HAVE AWNINGS AT STANCHION TUBE CENTERLINES) 4 X 8 PRESSURE TREATED BEAM FOR AWNING TO BOLT TO (TYP)

10'-4 21" (CNTR TO CNTR) 10'-11 13 16"

3 1'-7 16 "

3 1'-7 16 "

SECTION AW-AW BACK

O V

2'-0"

2'-0" TYP

U

3 9/16" X 1 9/16" X 0.033" 4 X 8 PRESSURE TREATED BEAM FOR STANCHION TUBE MOUNTING (REQD. ON SIDES THAT HAVE AWNINGS AT STANCHION TUBE CENTERLINES)

10'- 41"

11'-1"

V

7'-9" (CNTR TO CNTR)

AW

O

7 8'-3 16 "

3 1'-4 16 "

3 1'-4 16 "

ROLL FROM THIS END, FACE UP

AW

SECTION O-O

FRONT 14'-3 38"

10" X 2" X 0.068" STRONGBACK TOP

2'-0" TYP

REQUIRED BLOCKING AT MID HEIGHT IF PARAPET IS OVER 7' TALL (USE TREATED WOOD IF WOOD)

5'-0"

1 8'-2 16 "

1/2" OSB

5'-1 81"

4'-0"

5'-1 81"

DETAIL U SCALE 1 : 8

SECTION V-V Drawing Scale

Plot Scale:

0.25:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING LARGE PARAPET

00

PRELIMINARY USE ONLY

47

03/04/21 EDK BY APPROVAL REV DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

BACK 14'-3 38"

W X

Y 11'-1"

Y

2'-0" TYP

ROLL FROM THIS END, FACE UP

2'-0"

SECTION W-W

3 9/16" X 1 9/16" X 0.033"

W 10" X 2" X 0.068" STRONGBACK TOP

2'-0" TYP

1/2" OSB

ROLL FROM THIS END, FACE UP

FRONT

2'-0"

DETAIL X SCALE 1 : 8

5'-0"

SECTION Y-Y

Drawing Scale

Plot Scale:

0.375:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING SMALL PARAPET

PRELIMINARY USE ONLY

48

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

(2) PARAPETS TOTAL, ONE EACH SIDE OF BUILDING 9/16" OSB SHEATHING

22'-1 21" 2'-0"

10" X 2" X 0.0713" STEEL STUD STRONGBACK

2'-6"

2'-0" TYP

3.6942" X 1.6595" X 0.0346" C-CHANNEL

ROLL FROM THIS END, FACE UP

3 5/8" X 1 5/8" X 0.035" STEEL STUD

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING PARAPET WALL (1L & 1R)

PRELIMINARY USE ONLY

49

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

9 16" TYP

4 38"

1

1 21" TS

1 2" TS

16 "

7

4 1 4"

R1" 5 8"

R.025 TYP

ROLL FROM THIS END, FACE UP

4"

TS 1 2"

2 58"

4 41"

2

4

1 "

4

"

16

(6X) -

R.025 TYP

4 41"

3 8"

13

1

1 81" TS

2"

3 4"

9 16"

3" STS

(6X) -

R1"

2

(16ga.)

3 8" THICK EYE

R1"

2'-0"

FRONT AWNING

3

(3X) 4" x 2" x 1/8" 2'-0"

SIDE AWNING

C4 X 4.5

8'-0"

6'-0" 11 3 16 "

11 3 16 "

6'-0"

10'-8"

(1X) 4" x 2" x 1/8"

ROLL FROM THIS END, FACE UP

C4 X 4.5

9 16"

(6X) 2"

(5X) 4" x 2" x 1/8"

1 16"

3 2"

1 16" (16ga.)

6"

1 2 16 " 1 2 16 "

TS = TO SHARP STS = SHARP TO SHARP Drawing Scale: Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING AWNINGS

PRELIMINARY USE ONLY

50

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00 POST UNDER COUNTER FOR STRUCTURAL SUPPORT

COUNTER TOP LAYOUT

PLAM

AY

4'-0 1/2" 3'-0 1/2"

8'- 58"

2'-3"

2'-10" 3'-1"

FRONT COUNTER

2'-3"

7'-11 3/4"

4'-2 1/2"

3'-2"

1'-2 21"

3"

2 21"

ROLL FROM THIS END, FACE UP

8'-7" 8'-7"

ADJUSTABLE SHELF

6" TOE

12'-6 58"

DOORS

3'- 21" 2'-6 21"

1 3'-2 16 "

OPTIONAL 4TH ESPRESSO CUTOUT

PLAM

FRONT COUNTER

8 34"

DETAIL AY SCALE 1 : 4

3'-2"

PLAM

LEFT COUNTER

9'-10 34"

PLAM

2'-10" 3'-1"

5 34"

2'-3"

2'6"

2'-3"

2'-3"

PLAM PLAM

9'-5 34"

3"

ALL COUNTERTOPS HAVE 16GA STAINLESS TOPS OVER 1 1/2" (2X 3/4") MDX

9'-8 34"

RIGHT COUNTER

1 1 16 "

8 34"

10 58"

9 15 16"

PLAM

3"

1'-11 58"

2'-6"

2'-6"

2'-6"

2'-6"

2'-6"

14'-11 38" 15-5 38"

(3) FIXED SHELVES

9 15 16"

PLAM PLAM PLAM

6" TOE

6" TOE

ALL (3) ADJUSTABLE SHELF

ROLL FROM THIS END, FACE UP

8 34"

6" CLEAR SPACE INSIDE JAMBS

2'-6 21" 3'- 21"

(4) DRAWERS

11 1'-1 16 "

1 3 16 "

11 21"

3/4" SUPPORT PIPE W HUBS

7 21"

16'-8"

RIGHT COUNTER

9 15 16" 6" TOE

(3) FIXED SHELVES

6" TOE

6'-2 58"

3'-2"

OPTIONAL

9 15 16"

VERIFY AGAINST SINK CUTOUT TEMPLATE

3'- 41"

7 41"

3'- 41"

5 5 16 "

PLAM 10 21"

PLAM 3"

2'-10" 3'-1"

LEFT COUNTER

CABINETS ARE LABELED, VIEWS MAY SHOW STRETCHERS OR BLOCKING THAT MAY NOT BE THE SAME CONSTRUCTION AS THE MANUFACTURED PRODUCT, THIS DRAWING IS REPRESENTATIONAL ONLY. Drawing Scale: Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING CABINET DRAWINGS AND LAYOUT

PRELIMINARY USE ONLY

60

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

ROLL FROM THIS END, FACE UP

REVISION

00

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING BUILDING COLOR SPECS

PRELIMINARY USE ONLY

52

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

CEILING PANELS

WALL PANELS 15 5/16

4 3/4 16 13/16

22 7/8

22 7/8

22 9/16

27

10 1/2

31 15/16

W6

69 3/4

4 13/16

ROLL FROM THIS END, FACE UP

15 5/16

26

21 1/16

26

20

14 1/4 SPL 31 15/16

16 5/8

F1

SPL 31 15/16

6 1/16

F2

16 5/8

NSF LABEL R

Installation site floor must be true and level within 3/16" per 10' or additional costs may be incurred.

53

00 REV

03/04/21 EDK BY APPROVAL DATE

16 13/16

THE MINIMUM BTU'S SHOWN ARE BASED ON NSF STANDARD #7, SECTION 5, PARAGRAPH 5.36.7, REQUIREMENTS (REF. TABLE 1). THESE NUMBERS ARE NOT INTENDED TO BE USED FOR SIZING OF REFRIGERATION UNITS FOR THIS WALK-IN. IMPERIAL BROWN RECOMMENDS CONSULTING WITH A QUALIFIED ENGINEER OR CONTRACTOR CONTRACTOR.

22 7/8

PRELIMINARY USE ONLY

SPL 22 7/8

ELECTRICAL Field electrician to verify maximum acceptable load for light switches.If load is too high, then relay type controls should be used. After wiring devices, ALL conduits must be sealed to stop moisture transfer through electrical raceways. Failure to seal device per NEC codes WILL VOID WARRANTY.

15 5/16

60 1/16

Imperial Brown's sliding and vertical lift doors shall not be considered means of egress. Check code egress requirements for your application.

N.S.F. LISTED (STD #7) N.S.F. GASKET @ ALL PANEL JOINTS BTUS1 BTUs2 BTUs3

CP

9 1/4

COMPONENT

HBC-O6S

24 1/16

4 3/4 SPL

SPL 122 5/8

STANDARD NOTES To prevent condensation, a minimum 2" from the walk-in exterior surface is required. High humidity conditions may require force ventilation in addition to clearance.

Internal ID:

69 3/4B DC 69 3/4V DC

FLOOR PANELS

NOTES Meets 2009 Federal Energy Independence and Security Act Requirements.

Plot Scale:

$SWITCHINDEX 48 PNL T

00_RefNo 01_PageNo

PARTS (1) ea. Kason #1808 vapor proof LED light fixture (14W, 90-305V, 0.12A) - (LED lamp built-in.)

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING WALK-IN COOLER SPECS

SPL [A]

24

[B]: (3) 23" x 67" CDS FS Legacy Series cooler glass door (black frame) w/ lights & (5) rows of 27" deep shelves (Black)

0.5:12 1:1

[B] V1.B B1.B

31 15/16

SPL 31 15/16

CP

C2

SPL

DOORS [A]: 36" x 78" flush model G3 self-closing cooler door *** LEAF WILL NOT BE RAISED UNLESS SPECIFIED OTHERWISE *** Brand: Imperial Brown Frame: 4" high density urethane, 3-sided w/ Stucco galvalume both sides w/ 24 ga. stainless steel 430 (magnetic) liners w/ 3/4" stub-through concealed PVC conduit Leaf: 4" thick, 3-side lap, standard height w/ Stucco galvalume both sides w/ Magnetic gasket (3) Component Hardware #W59 spring assisted adjustable hinge (1) Component Hardware W19 latch (no lock, chrome) (1) Component Hardware #W28 inside release (1) Kason #1094 hydraulic door closer (1) Single pole toggle switch w/ pilot light (120V, 10A max. load) @ ext. (1) 2" flush mount analog thermometer w/ 12" capillary (1) .080 smooth aluminum threshold 36" high AFF .063 aluminum diamond tread (LP) kickplate (leaf, ext.)

Drawing Scale:

W5

W3

4 3/4

COOLER

C1

9 1/4

15 5/16

W4

W2

16 5/8

47

W1

FLOOR PANELS Model

Hand-Truck Floor panels model #HTFN (NSF) Construction: 3 1/2" high density urethane w/ .080 smooth aluminum @ interior over 1/2" plywood w/ Metal @ exterior

16 5/8

47

DC 47

6 1/16 5'-4" [64]

CEILING PANELS Construction

4" high density urethane Exterior Finish: Metal Interior Finish: Stucco galvalume Ceiling Caps: Factory mounted Live Load: 10 psf

SPL 31 15/16

SPL 122 5/8

DC 4 3/4 18 7/8

ROLL FROM THIS END, FACE UP

10'-2 5/8" [122 5/8]

12 1/8

26

21 1/16

26

20

WALL PANELS Construction

4" high density urethane Exterior Finish: Stucco galvalume Interior Finish: Stucco galvalume Ceiling connections: Camlock Floor connections: Camlock

SHELVES

14 1/4

SPECIAL INSTRUCTIONS Standard crating

W7

SPECIFICATIONS Indoor cooler (+35°F) (with floor) Vinyl foam NSF gasket (1/16" joint thickness), Cam-lock layout #4

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

1 1/2

1 1/2 2 1/2

1 1/4

UP1

2 1/4

48 24

ROLL FROM THIS END, FACE UP

UP4

2 3/4

Tension Break

21 1/2

UP2

Edge of box

1 3/4

30 3/16

UP3

S 84 3/4

2 1/4

NOTE

Due to construction variables seal threshold/jamb joint w/ silicone

11 5/8

4 Internal ID:

HBC-O6S

3" Metal return @ int.

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING WALK-IN COOLER SPECS

5'-7 1/8" [67 1/8] opening

36 AFF

Wall panel Wear surface

3 1/2

Concrete slab (By others than IB)

4 1/4

1/4 "NSF

3 01_REFNO 00_PAGENO

1/2

1/2" Plywood

No Cams

01_REFNO 00_PAGENO

3

6

6 base

4 1/4 Plot Scale:

75 15/16

[B] B1.B

36

INT.

SPL

75 15/16

ELEVATION 00_REFNO 01_PAGENO

0.5:12 1:1

V1.B

6

5 13/16 5 13/16

S

[A]

Drawing Scale:

5 13/16 5 13/16

SPL

7'-0 3/4" [84 3/4]

7'-9" [93]

T

[A]

EXT.

ROLL FROM THIS END, FACE UP

10'-0 1/8" [120 1/8]

2 1/2

30 3/16

Conduit ceiling holes to be drilled at jobsite (By others than IB)

9

39 3/16

48

15.0

°

1 1/4

4

36 3/4

1 3/4

9

Field drill & countersink (8) 5/16" holes for #14 x 1" FHSMS (CAUTION: Avoid heat cable)

1 3/4

T

PRELIMINARY USE ONLY

54

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

FRONT INTERIOR

ROLL FROM THIS END, FACE UP

DRY STORAGE

LEFT INTERIOR

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING INTERIOR IMAGES

RIGHT INTERIOR

PRELIMINARY USE ONLY

55

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

Digital Order Station

Digital Pre-Order Board ROLL FROM THIS END, FACE UP

Base Plate Detail 1'-6 1/2" 1'-1/2" 6"

BUILDING WALL 1" 1.5" 2"

10"

1'-1/2"

SPEAKER

MIC

1" conduit (1) 120V Static (Lighting) w/ pull string to electrical panel (1) 120V Digital w/ pull string to electrical panel 2" conduit with pull string for CAT 6 cable

1" conduit Loop from street

1.5" conduit with pull string future needs / Loop with Speaker / MIC ASPHALT DRIVEWAY

VEHICLE DETECTOR LOOP

SPEAKER / MIC

CAT 6

120 V AC

SPEAKER

ROLL FROM THIS END, FACE UP

MAGNETIC LOOP

MIC

3/4" MAGNETIC LOOP (CONNECT UNDER OR THROUGH FOUNDATION) 3/4" MAGNETIC LOOP

Drawing Scale

Not to Scale Plot Scale: Internal ID:

HBC-O6S

1:1

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING MENU BOARD CONDUIT SPECS

PRELIMINARY USE ONLY

56

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

REVISION

00

7' Menu Board

2'

4' 2'

2' Order Board w/ Speaker

45° 3.5' Speaker Post

90° Curved Lane Menu Board w/ Speaker

90° Curved Lane Menu Board & Speaker

4' 10'

4'

2' 2'

2' 5'

2'

ROLL FROM THIS END, FACE UP

4'

ROLL FROM THIS END, FACE UP

Straight Lane Menu Board w/ Speaker

Straight Lane Menu Board & Speaker

2' Order Board w/ Speaker

Speaker Post

Menu Board

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING MENU BOARD PLACEMENT

PRELIMINARY USE ONLY

57

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

ROLL FROM THIS END, FACE UP

REVISION

00

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING DRIVE THRU WINDOW SPECS

PRELIMINARY USE ONLY

58

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

ROLL FROM THIS END, FACE UP

REVISION

00

UPS

TOAST MERAKI ROUTER

Internet

SWITH FOR MERAKI ROUTER ITEMS

AUXILIARY ROUTER

Internet

ROLL FROM THIS END, FACE UP

SWITH FOR AUXILIARY ROUTER

Drawing Scale

Plot Scale:

0.5:12 1:1

Internal ID:

HBC-O6S

THE HUMAN BEAN 13'6" X 45' PREFABRICATED BUILDING LOW VOLTAGE RACK

PRELIMINARY USE ONLY

59

00 REV

03/04/21 EDK BY APPROVAL DATE

PRELIMINARY COPY REVISION NOTES

PROJECT REVIEW

THIS DOCUMENT CONTAINS CONFIDENTIAL OR PROPRIETARY INFORMATION OF HUMAN BEAN. NEITHER THE DOCUMENT NOR THE INFORMATION THEREIN IS TO BE REPRODUCED, DISTRIBUTED, USED OR DISCLOSED, EITHER IN WHOLE OR IN PART, EXCEPT AS SPECIFICALLY AUTHORIZED BY HUMAN BEAN.

CAD DRAWING. NOT TO BE MODIFIED MANUALLY.

End of document