PHOTOVOLTAIC GROUND MOUNT SYSTEM 64 MODULES - SYSTEM SIZE STC (26.880 kW DC / 24.576 kW AC) 1822 LAKE ROAD, WEBSTER, NY 14580, USA (43.274096, -77.3814947) SYSTEM SUMMARY STC (26.880 kW DC / 24.576 kW AC)
●
SHEET INDEX
' 80.02
(64) 420W = 26.880 kW STC AC: (64) 384W = 24.576 kW ● (64) SILFAB SOLAR INC. SIL-420 BG MODULES ● (64) ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] MICROINVERTERS
PV-1 PV-2 PV-3 PV-3.1 PV-4 PV-5 PV-6 PV-7+
8x BRANCH OF 8 CONNECTED IN PARALLEL
GOVERNING CODES 2020 NEW YORK STATE FIRE CODE 2020 BUILDING CODE OF NEW YORK STATE 2020 NEW YORK STATE RESIDENTIAL CODE 2017 NFPA 70 - NATIONAL ELECTRICAL CODE
GENERAL NOTES
3)
4)
5) 6)
ARRAY LOCATION(S)
299.76
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
' meas
.
'
2)
ALL PANELS, SWITCHES, ETC. SHALL HAVE SUFFICIENT GUTTER SPACE AND LUGS IN COMPLIANCE WITH UL REQUIREMENTS TO ACCOMMODATE CONDUCTORS SHOWN. THIS SYSTEM WILL NOT BE INTERCONNECTED UNTIL APPROVAL FROM THE LOCAL JURISDICTION AND UTILITY IS OBTAINED. ALL EXTERIOR ELECTRICAL DEVICES AND EQUIPMENT INCLUDING THOSE THAT ARE EXPOSED TO OUTSIDE ENVIRONMENT SHALL BE WEATHERPGROUND AND SHALL BE LISTED BY 'UL' FOR THE TYPE OF APPLICATION AND 'UL' LABEL SHALL APPEAR ON ALL ELECTRICAL EQUIPMENT. WIRING METHOD SHALL BE EMT ABOVE GROUND MOUNTED IN CONCEALED SPACES (UNLESS APPROVED OTHERWISE) AND SCHEDULE-40 PVC FOR BELOW GROUND INSTALLATIONS UNLESS NOTED OTHERWISE. AN OSHA APPROVED LADDER PROVIDING ACCESS TO ALL PORTIONS OF THE ARRAY SHALL BE SECURED IN PRIOR TO REQUESTING INSPECTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSTALL A SUPPLEMENTAL GROUNDING ELECTRODE CONDUCTOR IF NECESSARY.
595.56
1)
WEBSTER (TOWNSHIP OF), NEW YORK UTILITY: ROCHESTER GAS & ELECTRIC CORP
264.95 '
● ● ● ●
COVER PAGE GROUND MOUNT PLAN WITH MODULES RACKING DETAIL ATTACHMENT DETAIL SINGLE LINE DIAGRAM WIRING CALCULATION PLACARDS EQUIPMENT SPECIFICATION
UM
HOMEOWNER INFO
485.91
'
(E) STRUCTURE
JB1
GATE
FRONT OF HOUSE
DRIVEWAY
DIMENSIONS
OBSTRUCTION
PROPERTY LINE AC JUNCTION BOX (NEW) AC JUNCTION BOX
JB2 (NEW)
GT
2 PROPOSED 12' x 50' SOLAR ARRAYS
JB1
CBA
70.12'
LEGEND
5'
175.1
FENCE
NEW PV MODULE
JB2
SHEET NAME
25' 42.5'
COVER PAGE
#1
MSP
MAIN SERVICE PANEL (EXISTING, 200A)
PM
REVENUE GRADE METER (NEW)
CBA
AC COMBINER PANEL (NEW)
UM
UTILITY METER (EXISTING)
DA
AC DISCONNECT FUSED (NEW)
GT
IQ GATEWAY (NEW)
59.7'
77.7'
PROJECT SITE
533.75' meas
.
VICINITY MAP
1/100"=1'-0"
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
NTS
DAVID STERN
HOUSE PHOTO
1822 LAKE ROAD, WEBSTER, NY 14580, USA
MSP DA
PM
NTS
LAKE ROAD
SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-1
MODULE AREA & WEIGHT CALCULATIONS PV PANELS (COUNT, AREA, WEIGHT): ● (64x) SILFAB SOLAR INC. SIL-420 BG (73.4" x 40.5", 45.8 LB)
UM
MICRO-INVERTERS (COUNT, WEIGHT): ● (64x) ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (2.43 LB)
BILL OF MATERIALS EQUIPMENT
QTY
DESCRIPTION
SOLAR PV MODULES MICRO INVERTERS
64 64
JUNCTION BOX (AC)
2
LOAD CENTER (AC) IQ GATEWAY PRODUCTION METER
1 1 1
AC DISCONNECT
1
ATTACHMENTS
-
SILFAB SOLAR INC. SIL-420 BG ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] JUNCTION BOX 600V, NEMA 3R UL LISTED AC COMBINER PANEL ENPHASE IQ GATEWAY REVENUE GRADE METER PV VISIBLE LOCKABLE LABELED DISCONNECT (200A FUSED 1PH 240VAC) KRINNER G76X2100-4XM16 - REFER TO PAGE NO:(PV-11 TO PV-16.1)
ACES
DA
7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA
PM
15859357186
GROUND MOUNT DESCRIPTION
Steve@aces-energy.com
ARRAY
ARRAY TILT
AZIMUTH
#1
30°
165°
LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DESIGN CRITERIA ● ● ●
DATE
REV
EXPOSURE CATEGORY = C WIND SPEED = 110 MPH SNOW LOAD = 40 PSF
SIGNATURE & SEAL
LEGEND
FIRE SETBACK
RAFTER/TRUSS
OPTIMIZER
RAIL
MICRO-INVERTER
CONDUIT
GROUND ATTACHMENT
OBSTRUCTION
GT
JB1
SHEET NAME
CBA JB1
AC JUNCTION BOX (NEW) AC JUNCTION BOX
JB2 (NEW)
MSP
MAIN SERVICE PANEL (EXISTING, 200A)
PM
REVENUE GRADE METER (NEW)
CBA
AC COMBINER PANEL (NEW)
UM
UTILITY METER (EXISTING)
DA
AC DISCONNECT FUSED (NEW)
GT
IQ GATEWAY (NEW)
LAKE ROAD
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
FRONT OF HOUSE
NEW PV MODULE
1822 LAKE ROAD, WEBSTER, NY 14580, USA
CONDUIT IN TRENCH 18'' DEEP ~341' LENGTH 2" PVC CONDUIT
DAVID STERN
HOMEOWNER INFO
CONDUIT IN TRENCH 18'' DEEP ~25' LENGTH 2" PVC CONDUIT
GROUND MOUNT PLAN WITH MODULES SHEET SIZE
ANSI B 11" X 17"
JB2
SHEET NUMBER
GROUND MOUNT PLAN WITH MODULES SCALE: 3/128" = 1'-0"
#1
PV-2
CANTILEVER 7" 6' 10" E-W PIER SPACING
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA
7' 6" N-S PIER SPACING
15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
49' 2" CROSS PIPE
2'
8"
1' 10"
3' 11"
NORTH CLEARANCE
7' 6" SHEET NAME
5'
SCREW LENGTH
5' 3"
1' 4"
SOUTH CLEARANCE
2' 4"
30°
8' 3"
CA
6' 8"
N
IL RA
8' 4"
8" 16
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
R
VE
E TIL
1822 LAKE ROAD, WEBSTER, NY 14580, USA
IL RA
DAVID STERN
HOMEOWNER INFO
RACKING DETAIL
N-S PIER SPACING
SHEET SIZE
2' 4" 12' 1"
NTS
ANSI B 11" X 17" SHEET NUMBER
PV-3
CANTILEVER 7" 6' 10" E-W PIER SPACING
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186
7' 6" N-S PIER SPACING
Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
49' 2" CROSS PIPE
8"
1' 10"
3' 11"
NORTH CLEARANCE
SHEET NAME
7' 6"
RACKING DETAIL
5'
SCREW LENGTH
5' 3"
1' 4"
SOUTH CLEARANCE
2' 4"
30°
8' 3"
2'
8' 4"
C
6' 8"
IL RA
8" 16
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
R
E EV L I T AN
1822 LAKE ROAD, WEBSTER, NY 14580, USA
IL
RA
DAVID STERN
HOMEOWNER INFO
N-S PIER SPACING
SHEET SIZE
2' 4"
NTS
ANSI B 11" X 17" SHEET NUMBER
12' 1"
PV-3A
XR1000 Rail
UNIVERSAL FASTENING OBJEC PV MODULE
ACES
PV MODULE
7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186
XR1000 RAIL
XR1000 RAIL
Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
3” RAIL CONNECTOR
3” RAIL CONNECTOR
SIGNATURE & SEAL
3” PIPE/TUBING
3” TOP CAP
3” TOP CAP
3” PIPE/TUBING
Clamp Detail
UNIVERSAL FASTENING OBJECT
PV MODULE FRAME UNIVERSAL FASTENING OBJECT
RAIL 1”
PV MODULE FRAME
ATTACHMENT DETAIL
NTS
Mid Clamp, Front
1”
UNIVERSAL FASTENING OBJECT
UNIVERSAL FASTENING OBJECT
SHEET NAME
RAIL
RAIL
Mid Clamp, Plan
PV MODULE FRAME
STOPPER SLEEVE
STOPPER SLEEVE
End Clamp, Plan
DAVID STERN
Side View
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
Front View
1822 LAKE ROAD, WEBSTER, NY 14580, USA
HOMEOWNER INFO
PV MODULE FRAME
End Clamp, Front
ATTACHMENT DETAIL SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-3.1
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
2
INTERCONNECTION 120% RULE (MAIN PANEL) INTERCONNECTION 120% RULE NOT REQUIRED
8 MS-01
12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
LINE-SIDE PANEL CONNECTION DOES NOT AFFECT MAIN BUS
SYSTEM SUMMARY STC (26.880 kW DC / 24.576 kW AC)
EXTREME CASE MODULE OUTPUT (SILFAB SOLAR INC. SIL-420 BG)
(64) 420W = 26.880 kW STC AC: (64) 384W = 24.576 kW ● (64) SILFAB SOLAR INC. SIL-420 BG MODULES ● (64) ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] MICROINVERTERS
Isc(25°C) = 11.40A, Tisc = 0.046%/°C Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)] Isc(-16°C) = 11.18A, Isc(29°C) = 11.42A
●
8x BRANCH OF 8 CONNECTED IN PARALLEL
Voc(25°C) = 46.36V, Tvoc = -0.279%/°C Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)] Voc(-16°C) = 51.66V, Voc(29°C) = 45.84V
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
2
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186
8 MS-01
12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
2
Steve@aces-energy.com LICENSE #: N/A in New York State
TO CONSUMPTION CTs
REVISIONS
MCB-01
DESCRIPTION
MCB-01 MCB-01 MCB-01
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
JUNCTION BOX 600V, NEMA 3R UL LISTED
8
MAIN SERVICE PANEL (EXISTING, TOP-FED) BUS RATING: 200A MAIN BREAKER: 200A (E)
MS-01
BI-DIRECTIONAL UTILITY METER:18 823 068 UTILITY: ROCHESTER GAS & ELECTRIC CORP SERVICE: 240V 60HZ 1PH
MS-01 15A
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
PV VISIBLE LOCKABLE LABELED DISCONNECT (200A FUSED 1PH 240VAC)
LC-01 20A(N) 20A(N)
200A(E)
8
20A(N)
M
20A(N)
MS-01 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
M
CT
20A(N)
2
REV
GATEWAY
12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
1
DATE
IQ GATEWAY (ENCLOUSER)
LC-01 150A(N)
SIGNATURE & SEAL
TO UTILITY GRID
LC-02 HOMEOWNER INFO
20A(N) 20A(N)
REVENUE GRADE METER
ON OFF
8
MS-02 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING) MOD: SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
2
TRENCH GROUND ROD
JUNCTION BOX 600V, NEMA 3R UL LISTED
MCB-02 MCB-02 MCB-02 MCB-02
8
MS-02 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
ELECTRICAL NOTES
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
2
1) 2) 3)
SHEET NAME
8
AC wire details
MS-02 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
2
8
MS-02 12 AWG Q-CABLE 06 AWG Cu BARE G (BOND RACKING)
Min Ampacity
Live
Neutral
MS-01
14.50A
12 AWG (Q-Cable)
-
MS-02
14.50A
12 AWG (Q-Cable)
-
MCB-01 MCB-02 LC-01 LC-02
14.50A 14.50A 126.40A 126.40A
(2) 10 AWG THWN-2 (2) 10 AWG THWN-2 (2) 2/0 AWG THWN-2 (2) 1/0 AWG THWN-2
2/0 AWG THWN-2 1/0 AWG THWN-2
Wire
SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
1
ALL GROUNDING TO COMPLY WITH NEC 690.47. GROUNDTOP CONDUIT SHALL BE LOCATED MIN. 7/8" ABOVE GROUND SURFACE. ALL TERMINALS SHALL BE MIN. 75°C RATED.
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
2
DAVID STERN
1
TRENCH
1822 LAKE ROAD, WEBSTER, NY 14580, USA
20A(N) MOD: SILFAB SOLAR INC. SIL-420 BG INV: ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] (1 BRANCH X 8 MICRO-INV)
NTS
Ground 06 AWG BARE (NOT IN CONDUIT) 06 AWG BARE (NOT IN CONDUIT) 10 AWG THWN-2 10 AWG THWN-2 06 AWG THWN-2 06 AWG THWN-2
Min EMT
Min PVC
Min RMC
-
-
-
-
-
-
1/2 in 2 in
1 in 1/2 in 2 in 2 in
1/2 in 2 in
SINGLE LINE DIAGRAM SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-4
SYSTEM SUMMARY STC (26.880 kW DC / 24.576 kW AC) STC DC: (64) 420W = 26.880 kW STC AC: (64) 384W = 24.576 kW ● (64) SILFAB SOLAR INC. SIL-420 BG MODULES ● (64) ENPHASE ENERGY INC. IQ8H-240-72-2-US [240V] MICROINVERTERS ●
8x BRANCH OF 8 CONNECTED IN PARALLEL
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
AC wire details Total Power
Conductor sets
ccConductors /conduit
Expected max temp
Adjusted ampacity (ampacity x temp derate x conduit fill derate)
#Modules
Conductor & neutral size
MS-01
8
240 V
14.50A
20 A
3.8 kW
1
2
29
25 x 1.00 x - = 25.00 A
12 AWG (Q-Cable)
MS-02
8
240 V
14.50A
20 A
3.4 kW
1
2
29
25 x 1.00 x - = 25.00 A
12 AWG (Q-Cable)
MCB-01 MCB-02 LC-01 LC-02
8 8 64 64
240 V 240 V 240 V 240 V
14.50A 14.50A 126.40 A 126.40 A
20 A 20 A 150 A 150 A
3.8 kW 3.4 kW 24.3 kW 24.3 kW
1 1 1 1
2 2 2 2
29 29 29 29
35 x 1.00 x 1.00 = 35.00 A 35 x 1.00 x 1.00 = 35.00 A 175 x 1.00 x 1.00 = 175.00 A 150 x 1.00 x 1.00 = 150.00 A
10 AWG THWN-2 10 AWG THWN-2 2/0 AWG THWN-2 1/0 AWG THWN-2
EGC size (Cu) 06 AWG BARE (NOT IN CONDUIT) 06 AWG BARE (NOT IN CONDUIT) 10 AWG THWN-2 10 AWG THWN-2 06 AWG THWN-2 06 AWG THWN-2
Max length
V drop
Min EMT size
Min PVC size
Min RMC size
Cu
50 ft
1.12 %
-
-
-
Cu
50 ft
1.01 %
-
-
-
Cu Cu Cu Cu
25 ft 50 ft 341 ft 10 ft
0.15 % 0.61 % 2.79 % 0.09 %
1/2 in 2 in
1 in 1/2 in 2 in 2 in
1/2 in 2 in
INTERCONNECTION 120% RULE NOT REQUIRED LINE-SIDE PANEL CONNECTION DOES NOT AFFECT MAIN BUS
ELECTRICAL NOTES 1) 2) 3) 4) 5) 6) 7) 8) 9) 10) 11) 12)
SIGNATURE & SEAL
Conductor metal
INTERCONNECTION 120% RULE (MAIN PANEL)
ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600V AND 90°C WET ENVIRONMENT. WIRING, CONDUIT, AND RACEWAYS MOUNTED ON GROUNDTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C.VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. PV EQUIPMENT SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH NEC 690. EXACT LOCATION OF AUXILIARY GROUNDING TO BE DETERMINED AT TIME OF INSTALL. EXISTING WIRES MUST BE REPLACED IF SMALLER THAN LISTED MINIMUM SIZES PER NEC 310.15(B)(16).
HOMEOWNER INFO
EXTREME CASE MODULE OUTPUT (SILFAB SOLAR INC. SIL-420 BG) Isc(25°C) = 11.40A, Tisc = 0.046%/°C Isc(T) = Isc(25°C) x [1 + Tisc x (T-25°C)] Isc(-16°C) = 11.18A, Isc(29°C) = 11.42A Voc(25°C) = 46.36V, Tvoc = -0.279%/°C Voc(T) = Voc(25°C) x [1 + Tvoc x (T-25°C)] Voc(-16°C) = 51.66V, Voc(29°C) = 45.84V
SHEET NAME
WIRING CALCULATIONS SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
WIRING CALCULATIONS
NTS
REV
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
Min OCPD
1822 LAKE ROAD, WEBSTER, NY 14580, USA
Backfeed *1.25 /cond. set
DAVID STERN
WireID
Nominal Voltage
DATE
PV-5
! WARNING
! WARNING
ELECTRICAL SHOCK HAZARD
INVERTEROUTPUTCONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE
UTILITY INTERCONNECTION DISCONNECT (MSP OR AC DISCONNECT), AND WHEREVER REQUIRED BY AHJ (DC DISCONNECTS, INVERTERS) CODE REF: NEC 2017 - 690.56(C)(3)
PV SYSTEM DISCONNECT NOMINALOPERATINGACVOLTAGE:
101.12 AMPS 240
VAC
AC DISCONNECTS, PV POINT OF INTERCONNECTION CODE REF: NEC 2017 - 690.54
AC DISCONNECT, PV BACKFEED BREAKER/POINT OF INTERCONNECTION CODE REF: NEC 2017 - 690.13(B)
MAIN PHOTOVOLTAIC SYSTEM DISCONNECT
! CAUTION
4)
DUAL POWER SOURCE SECOND SOURCE IS PHOTOVOLTIC
5)
MAIN PANEL CODE REF: UTILITY
6)
7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
TURNRAPIDSHUTDOWN SWITCHTOTHE "OFF"POSITIONTOSHUT DOWNPVSYSTEM ANDREDUCE SHOCKHAZARD INTHEARRAY.
SOLAR ELECTRIC PV PANELS
HOMEOWNER INFO
INTERCONNECTION POINT (MSP OR AC DISCONNECT IF LINE SIDE TAP) CODE REF: NEC 2017 - 690.12, NEC 2017 - 690.56(C)
CAUTION:
POWER TO THIS SERVICE IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS AS SHOWN
UTILITY METER MAIN SERVICE PANEL
PHOTOVOLTAIC SYSTEM METER
DISCONNECT PRODUCTION METER
PV PRODUCTION METER CODE REF: N/A
SHEET NAME
PLACARDS
! WARNING PHOTOVOLTAIC SYSTEM COMBINER PANEL
AC COMBINER PANEL (WHEN APPLICABLE FOR PV LOAD CENTER) CODE REF: N/A
ACES
SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN
INTERCONNECTION DISCONNECT FOR UTILITY ACCESS CODE REF: NEC 2017 - 690.13(B) OR UTILITY
DONOTADDLOADS
3)
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM
2)
ADJACENT TO BACKFEED BREAKER IN SUBPANEL/MSP (IF APPLICABLE) CODE REF: NEC 2017 - 705.12(B)(2)(3)(b)
SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF NEC 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ. SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE WORDS, COLORS AND SYMBOLS. LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING METHOD AND SHALL NOT BE HAND WRITTEN. LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4 - 2017, PRODUCT SAFETY SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED. DO NOT COVER EXISTING MANUFACTURER LABELS.
1822 LAKE ROAD, WEBSTER, NY 14580, USA
INVERTERS, DC & AC DISCONNECTS, DC & AC COMBINER PANELS (IF APPLICABLE) CODE REF: NEC 2017 - 690.13(B)
MAXIMUMACOPERATINGCURRENT:
1)
DAVID STERN
TERMINALSONBOTHLINE ANDLOADSIDESMAYBE ENERGIZEDINTHEOPEN POSITION
NOTES AND SPECIFICATIONS
IQ GATEWAY COMBINER PANEL
LAKE ROAD
SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
MSP CODE REF: NEC 2017 - 705.10
PV-6
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-7
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-8
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-9
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-10
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-11
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-12
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-13
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-14
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-15
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-16
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-16.1
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER
PV-17
ACES ADDRESS: 7288 RUSH LIMA RD, HONEOYE FALLS, NY 14472,USA PHONE: 15859357186 EMAIL: Steve@aces-energy.com LICENSE #: N/A in New York State
REVISIONS DESCRIPTION
DATE
REV
SIGNATURE & SEAL
037.03-1-33.1 PHONE: +15857037612 EMAIL: dstern@elliotstern.com
1822 LAKE ROAD, WEBSTER, NY 14580, USA
DAVID STERN
HOMEOWNER INFO
SHEET NAME
EQUIPMENT SPECIFICATION SHEET SIZE
ANSI B 11" X 17" SHEET NUMBER